6. Operation and Configuration of S3M UPS Models
and Battery Cabinets
6.3.4 Configuring the S3M25-50K UPS and Optimizing Charging of the
BP240V09/BP240V09K, BP240V40 and BP240V40L Battery Cabinets
Step 1: Setting the Battery Group
The Battery Group is Quantity 1 for every set of 20 batteries that are in and/or connected to the UPS model. For example, UPS
model S3M50K UPS has no internal batteries and is Battery Group 1 by default. However, to connect a BP240V40L cabinet
with 40 internal batteries to the S3M50K, the S3M50K UPS must be configured to Battery Group 2. To connect a second
BP240V40L cabinet to the S3M50K UPS, the Battery Group must be 4 (four sets of 20 batteries). Obtain the Battery Group
number based on the specific S3M UPS and Battery Cabinet models combination from the chart under Section 6.4.
The value can be 1 to 8. The default value is 1 for S3M UPS models without internal batteries.
Step 2: Setting the Battery Number
The battery number must remain at 20 for all S3M10-100K UPS models when connected to Tripp Lite external battery cabi-
nets designed for the S3M-Series UPS Series.
Step 3: Setting Single Battery (Ah) Capability
Change the Single Battery (Ah) Capability to the individual Ah capacity for one individual battery as follows for the specific
battery cabinet model:
• BP240V09/BP240V09K: the Single Battery (Ah) Capacity is 9
• BP240V40/BP240V40L: the Single Battery (Ah) Capacity is 40
• BP240V65/BP240V65L: the Single Battery (Ah) Capacity is 65
• BP240V100/BP240100L: the Single Battery (Ah) Capacity is 100
The Single Battery (Ah) values can be 7~2000.
Scroll to the next display screen by pressing the down arrow.