6. Operation and Configuration of S3M UPS Models
and Battery Cabinets
EOD Battery Volt: End of discharge voltage is the low voltage cutoff of the batteries during a battery mode operation. The
value can be 1.60~1.90. The default value is 1.67V/cell, or 10.02Vdc per battery.
Float Temp Compen Coeff: Modifies the voltage of compensation after enabling the switch. The value can be
0.001~0.007V/cell/°C. The default value is 0.003V/cell/°C.
Boost Charge Setting: Boost charge can be set to Disable or Enable. The default value is Enable.
No Battery Warning: Keep this alarm enabled if you want the UPS to provide a warning when no batteries are present. The
default value is Enable.
6.4 Configuration Reference Table for S3M10-50K UPS and
BP240V09/09K/09-NIB or BP240V40/40-NIB/40L/40L-NIB Battery
Cabinet Models
Configurations for S3M10-20kVA UPS with Internal Batteries
UPS with Intenal
batteries
S3M10K1B
10kVA
S3M10K2B
S3M10K3B
S3M15K2B
15kVA
S3M15K3B
20kVA
S3M20K3B
Qty. of
Battery
Battery
Cabinet
Cabinets
BP240V09K
1
BP240V09K
1
BP240V09K
1
BP240V09K
1
BP240V09K
1
BP240V09K
1
Step 1
Step 2
Step 3
Single
Battery
Battery
Battery
(Ah)
Group
Number
Capability
5
20
6
20
7
20
6
20
7
20
7
20
71
Step 4
Time (minutes) to
Max Charge
Charge Batteries to
Current (A)
9
6.75
9
8.1
9
9.45
9
8.1
9
9.45
9
9.45
Step 5
Aver Changing
Duration (min)
90% at 25°C
500
500
500
500
500
500