I.8.6
KEYPAD-MODIFIABLE REGULATION
VARIABLES
The adjustment variables that can be edited from the keyboard are
illustrated in the following table.
Label
Function
Cooling set point
Heating set point
Remote summer/winter enablement
(THCE)
Pressure transducer enablement
(KFI condensation control)
Password (technical service)
I.8.7
SETTING SUMMER AND WINTER SET-
POINTS
IMPORTANT!
When modifying or varying the machine's operating
parameters, make sure that you do not create
situations that conflict with the other set
parameters.
The user is authorised to adjust the summer and winter set-point values
within the adjustment limits indicated in Par. I.8.6.
If, for example, the Coo (summer set-point) parameter is set at 0, the
A05 parameter (antifreeze alarm set-point) must be adjusted in order to
prevent the machine from shutting down. The A05 parameter is
password protected, therefore it can only be modified by authorised
RHOSS
S.p.A. personnel.
Whenever the A05 parameter is assigned a value below 3°C it is
essential to use water mixed with a suitable percentage of ethylene
glycol.
To set the summer and winter set-points, proceed as follows:
Press the Prg key for 2 seconds to gain access.
By pressing the MODE key, it is possible to move onto the label that
makes it possible to set the winter set-point.
All manuals and user guides at all-guides.com
Limit of
Set
adjustment
value
-5÷25°C
12°C
25÷48°C
40°C
n
n
The display shows the Coo label
(summer set-point).
The HEA label appears on the
display (winter set-point).
Press the Prg key to access the modifiable value of the parameter
selected.
The MODE (UP) and ON/OFF (DOWN) keys
can be used to increase or reduce its value.
Once the desired summer or winter set-point value has been set, just
press the MODE and ON/OFF keys at the same time to memorize the
set value.
To return to the initial screen, press the MODE and ON/OFF keys at
the same time.
25
SECTION I: USER
The display shows the summer
set-point value.
The memorized set value
flashes on the display for a few
seconds. After this, the display
will show the Coo label if the
summer set-point value has
been memorized or HEA if the
winter set-point value has been
memorized.
The water inlet temperature will
be displayed.