Hitachi RCI 1.0FSN3Ei/P-N23NA Manual De Instalación página 16

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 19
INSTALLATION OF OPTIONAL AIR PANEL: P-N23NA
5 Set the corner fo the refrigerant connection portion of the
indoor unit to the position indicated as "Ref. Piping", and
hook the C-shapped hinge (2 positions) onto the U-shapped
hooks (2 positions) so that temporary positioning is available.
Electrical
control box
Stamp
"Ref Pipe"
U-shaped hook
(Q'ty 2)
6 Mount the air panel onto the air panel fixing position by using
the factory-supplied fixing screws (M6 cross screws).
Indoor unit undersurface
False ceiling
Fixing plate (Air panel side)
:Fix screw until this end touches it.
7 Check to ensure that there is no gap around the conctacting
surface between the indoor unit and the air panel. Any gap
may cause air leakage or dewing.
8 Attach the corner pocket covers after mounting air panel:
a. Hook the band at the rear side of the cover for the corner
pockets onto the pin of the panel as shown below.
Band
b. Hook the L-shapped nail located at the rear side of the
cover for the corner pockets onto the square hole of the
air panel.
L-shaped Nail
Fixing Nail (3 Portions)
!
C A U T I O N
If tighten long screws insufficient, may cause something wrong as
below.
10
PMML0253A rev.5 - 08/2016
All manuals and user guides at all-guides.com
Indoor unit
Hook
Fixing plate
Air panel
Long screw
(Q'ty 4)
Fixing plate (indoor unit side)
*
Sealing gasket
Panel
Long screw
Pin
Air Leakage
Smudge
If any gap has even though tighten long screws sufficient, readjust the
height of indoor unit.
No gap shall exist
It's able to adjust the indoor unit height by using wrench from the
corner pocket.
Wrench
Too considerable adjustment of height cause dewing from drain-pain.
Do not turn the air louver by hand. If moved, the louver mechanism
would be damaged.
?
N O T E
When the corner cover is to be removed after installing the air panel:
Insert a coin or a flat-tipped screwdriver into the groove -1- and turn it
gently downwards. Perform the same operation in grooves -2- and -3-.
Lift the corner cover and, once the securing tabs (3 positions) have been
removed, remove it.
Dewing
Louver
Coin or slotted
screwdriver
Corner position
dent part

Hide quick links:

Tabla de contenido
loading

Tabla de contenido