Toshiba RAV-GM901ATP-E Manual De Instalación página 23

Aire acondicionado (tipo split)
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 110
Are there scratches or dents on the existing pipes?
NO
Is it possible to operate the existing air conditioner?
YES
After the existing air conditioner is operated in
cooling mode for approx. 30 minutes or longer,*
recover the refrigerant.
Refer to "13 Refrigerant recovery"
For cleaning the pipes and recovering oil
Refrigerant recovery: Pump down method
Remove the existing air conditioner from the piping
and carry out flushing (nitrogen pressure 0.5 MPa)
to remove any remains inside of the pipe.
Was largely discolored oil or a large quantity
of remains discharged? (When the oil deteriorates,
the color of the oil changes to a muddy or
black color.)
NO
Connect the indoor / outdoor units to the existing
pipe.
Use a flare nut attached to the main unit for the
indoor / outdoor units. (Do not use the flare nut of
the existing pipe.)
Re-machine the flare machining size to size for
R32/R410A.
(Airtight test), Vacuum dry, Refrigerant charge, Gas
leak check
Test run
43-EN
YES
Existing pipes: Cannot be used.
Use new pipes.
NO
Nitrogen gas pressure 0.5 MPa
(If there is discharge of remains, it is judged that a
large quantity of remains are present.)
YES
Clean the pipes or use new pipes.
Piping necessary to change the flare nut / machining
size due to pipe compression
1) Flare nut width: H
Copper
pipe outer
Ø6.4
Ø9.5
Ø12.7
Ø15.9
diameter
For R32,
17
22
26
29
R410A
H
Same as
For R22
24
27
above
2) Flare machining size: A
Copper
pipe outer
Ø6.4
Ø9.5
Ø12.7
Ø15.9
diameter
A
For R32,
9.1
13.2
16.6
19.7
R410A
For R22
9.0
13.0
16.2
19.4
Becomes a little larger for R32/R410A
Do not apply refrigerator oil to the flare surface.
[2] Minimum floor area : A
Total
refrigerant
quantity*
h
0
M (kg)
2.000
2.035
2.070
2.105
2.140
2.175
2.210
2.245
2.280
2.315
2.350
2.385
2.420
2.455
2.490
3.5HP
2.525
2.560
2.595
2.630
2.665
2.700
2.735
2.770
2.805
(mm)
2.840
2.875
2.910
2.945
2.980
3.015
3.050
(mm)
* Total refrigerant quantity: Refrigerant quantity
precharged at factory + Additional refrigerant quantity
charged during installation
– 22 –
2
(m
)
min
Floor
Wall
Ceiling
standing
mounted
mounted
unit
unit
unit
0.6
1.8
2.2
2
A
(m
)
min
34.32
3.81
2.55
35.53
3.95
2.64
36.77
4.09
2.73
38.02
4.22
2.83
39.30
4.37
2.92
40.59
4.51
3.02
41.91
4.66
3.12
43.25
4.81
3.22
44.61
4.96
3.32
45.98
5.11
3.42
47.39
5.27
3.52
48.81
5.42
3.63
50.25
5.58
3.74
51.72
5.75
3.85
53.20
5.91
3.96
54.71
6.08
4.07
56.23
6.25
4.18
57.78
6.42
4.30
59.35
6.59
4.41
60.94
6.77
4.53
62.55
6.95
4.65
64.18
7.13
4.77
65.84
7.32
4.90
67.51
7.50
5.02
69.21
7.69
5.15
70.92
7.88
5.28
72.66
8.07
5.40
74.42
8.27
5.54
76.20
8.47
5.67
78.00
8.67
5.80
79.82
8.87
5.94
44-EN
Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Rav-gm901atjp-e

Tabla de contenido