Safety
The unit must be firmly secured to the soil.
It is essential to observe the following instructions:
The unit can only be lifted using the lifting points marked
in yellow fixed to its base.
It is forbidden to access the electrical components without
having opened the unit main switch and switched off the
power supply.
It is forbidden to access the electrical components without
using an insulating platform. Do not access the electrical
components if water and/or moisture are present.
Sharp edges and the surface of the condenser section
could cause injury. Avoid direct contact and use adeguate
protection device
Switch off power supply, by opening the main switch,
before servicing the cooling fans and/or compressors.
Failure to observe this rule could result in serious
personal injury.
Do not introduce solid objects into the water pipes while
the unit is connected to the system.
A mechanical filter must be installed on the water pipe
connected to the heat exchanger inlet.
The unit is supplied with safety valves, that are installed
both on the high-pressure and on the low-pressure sides
of the refrigerant circuit.
It is absolutely forbidden to remove all protections of
moving parts.
In case of sudden stop of the unit, follow the instructions on the
Control Panel Operating Manual which is part of the on-
board documentation delivered to the end user.
It is strongly recommended to perform installation and
maintenance with other people. In case of accidental injury or
unease, it is necessary to:
-
keep calm
press the alarm button if present in the installation site
-
move the injured person in a warm place far from the unit
-
and in rest position
Figure 2 - Operating limits
Operation with Glycol
(below 4°C Evap LWT)
-6
-4
-2
In this area Chiller may operate at
part load
0
2
4
Evap Leaving Water Temperature (°C)
contact immediately emergency rescue personnel of the
-
building or the Health Emergency Service
wait without leaving the injured person alone until the
-
rescue operators come
-
give all necessary information to the the rescue operators
Avoid installing the chiller in areas that could be
dangerous during maintenance operations, such as
platforms without parapets or railings or areas not
complying with the clearance requirements around the
chiller.
Noise
The unit is a source of noise mainly due to rotation of
compressors and fans.
The noise level for each model size is listed in sales
documentation.
If the unit is correctly installed, operated and manteined the
noise emission level do not require any special protection
device to operate continuosly close to the unit without any risk.
In case of installation with special noise requirements it could
be necessary to install additional sound attenuation devices.
Moving and lifting
Avoid bumping and/or jolting during loading/unloading unit
from the truck and moving it. Do not push or pull the unit from
any part other than the base frame. Secure the unit inside the
truck to prevent it from moving and causing damages. Do not
allow any part of the unit to fall during transportation or
loading/unloading.
All units of the series are supplied with lifting points marked in
yellow. Only these points may be used for lifting the unit, as
shown in the following.
Use spacing bars to prevent damage to the condensation
bank. Position these above the fan grills at a distance of at
least 2.5 metres
Both the lifting ropes and the spacing bars must be
strong enough to support the unit safely. Please check
the unit's weight on the unit nameplate.
Speedtroll required
(below -10°C Amb.)
6
8
10
.
D-EIMAC01008-16EU - 10/194
Fan
Speed
Modulation
required
(below 10°C)
12
14
16