Portable Wet Well Installation - Wilo EMU FA Instrucciones De Instalación Y Funcionamiento

Ocultar thumbs Ver también para EMU FA:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 96
en
4
1
5
6
Fig. 4: Wet well installation, stationary
6.4.4

Portable wet well installation

48
Installation and electrical connection
Work steps
1
Gate valve
2
Non-return valve
3
Suspension unit
4
Guide pipes (provided by the customer)
2
5
Attachment point for lifting equipment
6
Minimum water level
Operating space/installation location is prepared for the installation.
Suspension unit and pipe system were installed.
Pump is prepared for operation on the suspension unit.
3
1. Use a shackle to attach the lifting equipment to the attachment point of the pump.
2. Lift the pump, swivel it above the chamber opening and slowly lower the guide
claw onto the guide pipe.
3. Lower the pump until it sets on the suspension unit and is connected automatic-
ally. CAUTION! Hold the power supply cables slightly taut when lowering the
pump!
4. Loosen the lifting equipment from the lifting gear and secure it at the chamber
outlet against falling.
5. Have the power supply cables routed into the chamber by a qualified electrician
and route it outside properly from the chamber.
▶ The pump is installed, the qualified electrician can make the electrical connection.
WARNING
Risk of burns from hot surfaces!
Motor housing can become hot during operation. It may cause burns. Allow the
pump to cool down at ambient temperature after switching it off!
WARNING
Separation of pressure hose!
Separation or movement of the pressure hose can lead to (serious) injuries. Securely
attach the pressure hose to the outlet! Prevent buckling of the pressure hose.
NOTICE
Delivery problems due to water level being too low
If the level of the fluid is lowered too much, the volume flow can be interrupted. Air
cushions can also form in the hydraulics, which can lead to inadmissible operational
behaviour. The minimum permissible water level must reach the upper edge of the
hydraulics housing!
For portable installation, the pump must be equipped with a pump support foot. The
pump support foot ensures minimum ground clearance in the suction area and enables
secure footing if placed on a solid bearing surface. In this installation type, the pump
can be installed anywhere in the operating space/installation site. A hard base must be
used at the installation location to prevent sinking in case of soft bearing surfaces. A
pressure hose is connected on the pressure side. If operated for longer periods of time,
fix the pump firmly to the floor. This prevents vibration and ensures quiet and low-
wearing running.
WILO SE 2018-02
Tabla de contenido
loading

Este manual también es adecuado para:

Emu f-motor

Tabla de contenido