CONFIGURATION MENU
12.5.2 Set hysteresis for temperature differential ON-OFF
•
Following the path Menu -> CONFIG SEt -> CONTROL SEt -> select On:OFF,
and then press the button OK.
•
Using the 23 buttons, enter the required hysteresis value (values adjustable
from 0.2 °C to 1.2 °C / from 0.3 °F to 2.1 °F - by default 0.3 °C/0.4 °F).
•
Press the OK button to confirm.
•
Press the back button to exit.
12.5.3 Adjust period duration for the Modulating
proportional mode
•
Following the path Menu -> CONFIG SEt -> CONTROL SEt -> select PrOP,
and next press the OK button.
•
Using the 23 buttons, enter the required duration of the period (adjustable
from 7 to 20 min, by default 10 minutes).
•
Press the OK button to confirm.
•
Press the back button to exit.