Dip Switch Setting - Haier MRV Serie Instrucciones De Instalación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

ELECTRICAL WIRING

Dip Switch Setting

• The dip switch is set to the "On" position if "1" is indicated in the table. The dip switch is set to the "Off" position if "0" is
indicated in the table.
• Dip switches set in the factory to on are marked with red.
Definition principles of code switches:
(A) Definition of SW01:
• SW01_1-4 is used to set indoor address when grouping multiple indoor units connected to single wired controller
YRE16B or YR-E17.
• SW01_5-8 set capacity of the indoor unit (factory set). Must only set when replacing board.
SW01_1
Address of wire
SW01_2
controlled indoor unit
SW01_3
(group address)
SW01_4
SW01_5
Capability of indoor unit
SW01_6
SW01_7
SW01_8
Note : A wired controller can be connected to sixteen ultrathin air-duct indoor units.
(B) Definition and description of SW03
• SW03_1-8 is used to set indoor unit address on system. Set address only if using central controller YCZ-A004.
Leave default if no central controller is used.
SW03_1
Address of setting
mode
SW03_2
Code-set indoor unit
~
address and centralized
SW03_8
controller address
Note:
• Set the address by code when connecting the centralized controller, gateway or control system.
• Address of centralized controller = communication address + 0 or +64.
SW03_ 2=OFF, address of centralized controller = communication address + 0 = communication address
SW03_ 2=ON, address of centralized controller = communication address + 64 (applies when centralized controller is
used and there are more than 64 indoor units)
18
[1]
[2]
[3]
[4]
Address of wire controlled indoor unit (group address)
0
0
0
0
0# (wire controlled main unit) (default)
0
0
0
1
1# (wire controlled sub unit)
0
0
1
1
2# (wire controlled sub unit)
0
0
1
1
3# (wire controlled sub unit)
•••
•••
•••
•••
•••• •••
1
1
1
1
15# (wire controlled sub unit)
[5]
[6]
[7]
[8]
Capability of indoor unit
0
0
0
1
7000BTU
0
0
1
0
9000BTU
0
0
1
1
12000BTU
0
1
1
0
18000BTU
0
1
1
1
24000BTU
[0]
Automatic address setting or wired controller address setting (default)
1
Code-set address
[2]
[3]
[4]
[5]
[6]
[7]
[8]
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
0
1
0
•••
•••
•••
•••
•••
•••
•••
0
1
1
1
1
1
1
1
0
0
0
0
0
0
1
0
0
0
0
0
1
1
0
0
0
0
1
0
•••
•••
•••
•••
•••
•••
•••
1
1
1
1
1
1
1
Address of indoor unit
Address of centralized controller
0# (Default)
0# (Default)
1#
1#
2#
2#
•••
•••
63#
63#
0#
64#
1#
65#
2#
66#
•••
•••
63#
127#
31-5000500 Rev. 0
Tabla de contenido
loading

Este manual también es adecuado para:

Mvad007mv2aaMvad009mv2aaMvad012mv2aaMvad018mv2aaMvad024mv2aa

Tabla de contenido