Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Technical data

Type
Power supply
Nominal current
Nominal force
Nominal locking force
Lifetime
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Nominal stroke length*
Additional functions *
* Programmable with software SW-BSY+
Normal operation =
SHEV- fast running =
Forces
ZA 35
ZA 85
OPEN
300 N
800 N
CR III
300 N
800 N
CR II
300 N
800 N
CR I
300 N
800 N
Closing edge protection
In "CLOSE" direction the drive has an active
protection for the main closing edge. With an
overload in the closing range 3 and 2 the drive runs
"OPEN" for 10 seconds, then drive "CLOSE" again. If
after three attempts a closing is not possible, the
drive remains in this position.
In addition, the drive has a passive protection. The
closing speed in closure Range 2 and 1 is reduced to
5 mm/s.
Higher forces can occur on besides
closing edges. Danger of violent
pressure in handaccessible area.
8/20
ZA-BSY+
ZA35-BSY+(-HS)
ZA85-BSY+(-HS)
24 VDC, ±15%
24 VDC, ±15%
0,5 A (1,2 A)
1,0 A (2,0 A)
300 N
800 N
1100 N
>10 000 double strokes
30 % (With cycle time 10 minutes)
A
nodized aluminium / polycarbonate
IP 65
-5 ... +75°C
30 min / 300°C
S
ee type plate
C
losing edge protection activated (3 stroke repeatings)
ZA 105 ZA 155
1000 N
1500 N
1000 N
1000 N
All forces
1000 N
1000 N
+ approx. 20 % switch-off reserve
800 N
800 N
(temporary)
ZA105-BSY+(-HS)
24 VDC, ±15%
1,2 A (2,2 A)
1000 N
Running speed and forces
Main closing edge
English
ZA155-BSY+(-HS)
24 VDC, ±15%
1,4 A (2,5 A)
1500 N
99.824.31 1.2/03/12
Tabla de contenido
loading

Tabla de contenido