Technical data
Type
Supply
Active power
Apparent output
Nominal force
Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temperature range
Fire stability
Emission sound pressure LpA ≤ 70 dB(A)
level
Nominal stroke length *
Additional functions *
* programmable with software SCS and BI-BT2 via Bluetooth
Normal operation =
fast-mode SHEV =
Forces
ZA 35
ZA 85
OPEN
300 N
800 N
CR III
300 N
800 N
CR II
300 N
800 N
CR I
300 N
800 N
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing range 3 and 2, the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the drive
remains in this position.
In addition, the drive is equipped with passive pinch
protection. The closing speed in closing range 2 and
1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
99.823.99 1.7/02/16
ZA 35-K-BSY+(-HS)
ZA 85-K-BSY+(-HS)
230 V AC, +10 % / -15 %, 50 Hz
20 W (35 W)
30W (50 W)
30 VA (45 VA)
45 VA (75 VA)
300 N
800 N
1100 N
>20 000 double strokes
30 % S2 (EN 60034-1), no continuous voltage
aluminium / polycarbonate
IP 65 ("-W" = IP 54)
-5 ... +75°C
30 min / 300°C
see type plate
Closing edge protection activated (3 stroke repeatings)
ZA 105 ZA 155
1000 N
1500 N
1000 N
1000 N
All forces + approx.
1000 N
1000 N
20% cut-off reserve
800 N
800 N
(temporary)
ZA 105-K-BSY+(-HS) ZA 155-K-BSY+(-HS)
35 W (60 W)
55 VA (85 VA)
1000 N
Running speeds and forces
English
45 W (75 W)
70 VA (105 VA)
1500 N
main closing edge
ZA-K-BSY+
7/20