Selectable Device Functions - SICK MSM Instrucciones De Operación

Ocultar thumbs Ver también para MSM:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 71
Operating
Instructions
MSM
Note
Function
Sensor test
Concurrence monitoring (3 s)
Number of sensor pairs
Total muting time (60 s)
Factory default
(all switches down)
1
2
3
4
5
6
Table 2: Functions of the DIP switches
8 008 329/O371/05-04-04 © SICK AG • Industrial Safety Systems • Germany • All rights reserved
190
Product description
3.5

Selectable device functions

The device has selectable functions. They should be selected
to suit the respective application.
When the cap on the MSM is unscrewed, DIP switches can be
accessed to select the desired configuration. For this two DIP
switches must always be set in the same position, depending
on function (see Table 2).
The configurations are:
Ÿ Sensor test
Setting of whether testable or non-testable muting sensors are
connected.
Ÿ Concurrence monitoring
The sensors of one sensor pair must be activated within
3 seconds when the function is selected; otherwise no muting
is possible. The function is intended to protect against
manipulation (e.g. masking of an optical sensor). Therefore only
activates when the condition is satisfied.
Associated
switches
1 and 5
2 and 6
3 and 7
4 and 8
7
8
Function:
Off
On
Off
On
1 sensor pair
2 sensor pairs
Off
On
Switch setting
Up
Down
Section 3
Tabla de contenido
loading

Tabla de contenido