Important Safety Instructions
Select Hardwire Input/Output Models
CAUTION: To reduce the risk of fire, connect only to a circuit provided with maximum branch circuit
overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and the Canadian
Electrical Code, Part I, C22.1. See "UPS Input and Output Overview" table in the Installation section for
details.
• Use copper conductors with rated 221°F (105°C) wires only. See "UPS Input and Output Overview" table in the Installation
section for recommended input and output configuration.
• For models equipped with a permanent hardwire output connection, overcurrent protection is to be provided in the end-
use installation. Use output branch-rated overcurrent protection not exceeding the UPS/transformer Output rating. When
supplying receptacles with lesser branch-rated overcurrent protection, the overcurrent protection should match the
receptacle rating.
• When the hardwire AC output is used, appropriate OUTPUT OVERCURRENT protection must be provided by the installer. Be
sure to use branch-rated circuit breakers that match the rating of the receptacles/equipment being protected. Use circuit
breaker(s) with a C curve.
• Always use protective earth ground wire in the installation and between the UPS and transformer modules.
• An appropriate and readily accessible two-pole disconnect device must be incorporated in the fixed wiring.

Battery Warnings

See your UPS owner's manual.
4