4.4.3 Frequency measurement
Frequency sensors, which produce a frequency signal in the range
of 0 . . 9,99 kHz, can be directly combined with the SCE-020-03.
The following combinations are possible:
Decimal place FACt
00.02
000.1
00.02
Please note: The frequency signal must not exceed 5 V
Parameter configuration SCE-020-03 frequency measurement:
The following procedure applies to the parameter configuration:
1.
Set the decimal place (watch the indication range)
according to Section 4.2.1
2.
Set the K-factor according to the above table
M3 is selected with the + / - keys and the parameter
selection is activated with SET . Then enter the K-factor
with the + / - keys and confirm with SET . The setting is
ended with SET .
3.
Setting iPr = 0
Select M4 with the + / - keys and activate the parameter
selection with SET . Then enter iPr = 0 with the + / - keys
and confirm with SET . The setting is ended with SET .
4.
Saving the configuration
The parameter configuration is ended as soon as the iPr
value is confirmed with SET . This configuration is saved
with End . A further confirmation with End saves the
parameter configuration. The instrument switches
automatically into the operating mode Measuring and
Display .
iPr
Indication range
9999
1
0 . . 99,99 Hz
0999
1
0 . . 999,9 Hz
1000
0
0 . . 9,99 kHz
- 23 -
!!
SS