any air bubbles to be bled off through the
air valves. Should the pressure have risen
PT
well above the limit expected, discharge
the over pressure by opening the pressu-
re-relief valve.
GB
2.5. 1
Emptying the system (fig. 5)
GR
Use the drain tap to empty the system (9).
Turn off the boiler before doing this.
RO
2.6
FLUES/CHIMNEYS
The flue or chimney used to release the
RUS
products of combustion into the atmosphe-
re must comply with current legislation.
2.6. 1
Passing flue pipes through
an existing chimney
When renovating or passing flue pipes
through an existing chimney, use only flues
which are declared suitable for the purpo-
se by the manufacturer, following the
instructions for installation and use provi-
ded by the manufacturer.
2.7
INSTALLATION COAXIAL DUCT
(vers. "25 BF")
The air inlet-smoke outlet assembly ø
60/100 is supplied in a kit code 8084811
complete with mounting instructions.
With the curve supplied in the kit the
maximum horizontal length of the flue
must not exceed 3.4 metres.
The diagrams in fig. 6 illustrate a number of
examples of different coaxial outlets.
2.7. 1
Coaxial flue diaphragm
The boiler is normally supplied with ø 87.5
diaphragm. Insert the diaphragm only if the
length of the coaxial flue.
Refer to fig. 7 for positioning.
72
"25 OF" models
5
8
3 2
4
9
KEY
1 D.H.W. inlet/outlet manifold
2 Fill tap
3 D.H.W. filter
4 By-pass
y
KEY
1
Coaxial flue kit
code 8084811
x + y = max 3,4 m "25"
x + y = max 3,0 m "30-35"
2 a Extension L. 1000
code 8096100
2 b Extension L. 500 code 8096101
3
Vertical extension L. 200 code 8086908
4
Additional 90° curve code 8095800
6
Articulated tile code 8091300
7
Roof outlet terminal L. 1284 code 8091200
8
Vertical condensation collector L. 200 cód. 8092803
IMPORTANT:
– Each additional 90° curve installed reduces the available
length by 0.90 metres.
– Each additional 45° curve installed reduces the available
length by 0.45 metres.
– It is advisable to assemble the condensation collector
(8) on vertical segments exceeding 2.5 metres in length
and to limit maximum length to 4 metres.
With outlet type C12 - C42, install diaphragm ø 87.5 only if the coaxial flue is less
than 1.8 metres long.
With outlet type C32, use the following diaphragms, depending on flue length and without
any additional curves:
Installations with vetrical
extension L. 200 code 8086908
Optional
Standard
diaphragm ø 86 diaphragm ø 87,5
(cód. 6028623)
L min = 1,3 m
L min = 2,5 m
L max = 2,5 m
L max = 4 m
"25 BF" models
8
5
2
1
3
5 Water rate adjuster
6 D.H.W. exchanger
7 Microswitches
8 Water flow switch
9 Boiler discharge
x
2
4
3
C42
C32
max 3,4 m "25"
max 3,0 m "30-35"
C12
Installations with vertical condensation
collector code 8092803
Without
Standard
diaphragm
diaphragm ø 87,5
L min = 4 m
L max = 2,5 m
L max = 5 m
7 6
4
9
Fig. 5
7
6
2
8
3
1
Fig. 6
None
diaphragm
L min = 2,5 m
L max = 4 m
Fig. 7