4.1. TERMINAL BOARD CN1

4.1.1. P
22V
OWER SUPPLY
"VAC-VAC" terminals. The secondary circuit of the 24V~ 50/60 Hz transformer should be connected to this input. Power
supplied by the transformer is signalled by the lighting of the "ALIM" LED located under the terminal board.
4.1.2. B
ATTERIES
"+BAT - -BAT" terminals. Connect the power cables of the buffer batteries (optional) to these terminals. The control unit
is designed to operate with two buffer batteries, with the minimum characteristics shown on the table in paragraph
2. During normal operation, the unit keeps the batteries charged and these start operating if no power is supplied to
the transformer.
Power supplied by batteries only should be considered an emergency situation. The number of possible
manoeuvres is linked to the quality of the batteries, the structure of the gate to be moved, the time elapsed
since power cut occurred, etc, etc.
Observe the battery power supply polarity.
Observe the battery power supply polarity.
4.1.3. A
4.1.3. A
CCESSORIES
CCESSORIES
"+24V - -24V
+24V - -24V" terminals. The accessories power cables should be connected to these terminals.
The maximum load of the accessories must not exceed 500 mA.
The maximum load of the accessories must not exceed 500 mA.
The output of these terminals is DC - observe the power supply polarity of the accessories.
The output of these terminals is DC - observe the power supply polarity of the accessories.
4.1.4. E
4.1.4. E
ARTH
ARTH
"
" terminal. The control unit earthing cable should be connected to this terminal.
" terminal. The control unit earthing cable should be connected to this terminal.
This connection is absolutely necessary to ensure a correctly operating control unit.
This connection is absolutely necessary to ensure a correctly operating control unit.

4.2. TERMINAL BOARD CN2

4.2. TERMINAL BOARD CN2
4.2.1. G
4.2.1. G
1
1
EARMOTOR
EARMOTOR
"APM1 - CHM1
APM1 - CHM1" terminals. For double leaf applications, connect to these terminals the gearmotor fitted on the leaf
" terminals. For double leaf applications, connect to these terminals the gearmotor fitted on the leaf
which must move first. For single leaf applications, the gearmotor must be connected to these terminals. The maximum
which must move first. For single leaf applications, the gearmotor must be connected to these terminals. The maximum
load of the gearmotor must not exceed 70W.
load of the gearmotor must not exceed 70W.
4.2.2. G
4.2.2. G
2
2
EARMOTOR
EARMOTOR
"APM2 - CHM2
APM2 - CHM2" terminals. For double leaf applications, connect to these terminals the gearmotor fitted on the leaf
" terminals. For double leaf applications, connect to these terminals the gearmotor fitted on the leaf
which must move last. For single-leaf applications, nothing should be connected to these terminals. The maximum
which must move last. For single-leaf applications, nothing should be connected to these terminals. The maximum
load of the gearmotor must not exceed 70W.
load of the gearmotor must not exceed 70W.
4.2.3. E
4.2.3. E
LECTRIC LOCK
LECTRIC LOCK
"ELS - ELS"terminals. The electric lock, if any, with 12 Vdc/~ power supply, should be connected to these terminals. To
"terminals. The electric lock, if any, with 12 Vdc/~ power supply, should be connected to these terminals. To
facilitate release of the electric lock, the over-pushing stroke can be input by enabling parameter "F" (see paragraph
facilitate release of the electric lock, the over-pushing stroke can be input by enabling parameter "F" (see paragraph
9).
In double-leaf applications, install the electric lock on the leaf where gearmotor 1 is installed.
In double-leaf applications, install the electric lock on the leaf where gearmotor 1 is installed.
4.2.4. F
4.2.4. F
/ C
/ C
LASHING LAMP
LASHING LAMP
"LAMP - LAMP
LAMP - LAMP" terminals. Both a flashing lamp and a courtesy light can be connected to these terminals, both with 24
" terminals. Both a flashing lamp and a courtesy light can be connected to these terminals, both with 24
Vdc power supply and maximum 15W. To make this output operational, select parameter "G", see paragraph 9.
Vdc power supply and maximum 15W. To make this output operational, select parameter "
Flashing lamp operation:
Flashing lamp operation:
During normal operation, the flashing lamp provides a fixed pre-flashing of 1.5 seconds during both opening and closing.
When the gate is open, and the closing safety devices are tripped, the lamp flashes to indicate that a manoeuvre is
taking place in the gate movement area. We advise you to connect the flashing lamp before programming, because
it indicates its phases. Use a fixed light flashing lamp; flashing is controlled by the control unit.
Courtesy light operation:
The courtesy light stays lighted for a fixed time of 90 seconds from the OPEN pulse, after which it goes OFF. Use a lamp
with 24 V power supply and maximum 15W.

4. CONNECTIONS AND OPERATION

OURTESY LIGHT
OURTESY LIGHT
14
", see paragraph 9.