Troubleshooting - Ribind J Importantes Instrucciones De Seguridad Para La Instalación

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

On restoring of power a further command is necessary.
Upon command input the interrupted operation is completed (in case of opening, the open
stroke is completed...).
TECHNICAL DATA
Temperature range
Moisture
Power supply voltage
Frequency
Transient power mains drops
Max. power managed at the motor output
Max. load at the blinker output
Max. card power absorption (excluding the accessories) 20 mA
Current available for the photocells
Protection degree
Weight of the equipment
Dimensions
TECHNICAL FEATURES OF THE RADIO (CRX MODELS ONLY)
Frequency for the reception
Impedance
Sensitivity
Energizing time
De-energizing time
Codes to be memorized
Current available on the radio connector
- All inputs shall be used as clean contacts without earthing, because the power supply is
generated in the card and is structured in such a way to guarantee the respect of double
and reinforced insulation to the elements under voltage
- All inputs are managed by a programmed circuit that carries out a self-control every time
the door is operated.

TROUBLESHOOTING

After having carried out all connections, by carefully following the layout and having positioned
the gate in intermediate position, check the correct ignition of LEDS DL3, DL4.
In case of no ignition of the LEDS, always with gate in intermediate position, check the following
and replace any faulty components.
DL3 switched off
Faulty safety edge (In case the edge is not connected, carry out jumper
between COM and EDGE)
DL4 switched off
Faulty photocells
During functioning with personnel present, with DIP 1 to ON, check that during opening the
green DL7 LED switches on and that during closing the red DL6 LED switches on.
If not, invert clamps V and W on the motor terminal board.
After having carried out the various connections and having supplied voltage, all the LEDS are
switched off.
The motor opens and closes, but it has no strength and moves slowly.
The shutter opens but does not close after the time set.
The shutter does not open or close by activating the various K and RADIO buttons.
By activating the K button the shutter does not move.
0±55°C
<95% without condensation
230 V±10% (120 V±10% on request)
50/60 Hz
20 ms
1 CV
40 W with resistive load
0,4 A±15% 24 Vdc
IP 54
0,70 kg
14,7 x 6 x 18,5cm
433,92 MHz
52 Ω
>2,24 µV
300 ms
300 ms
N° 60
200 mA 12Vdc
FAULT
Check the integrity of fuses F1 and F2.
In case of interrupted fuse use only of adequate value F2 = 6,3A F1 = 100mA.
Check trimmer TORQUE adjustment.
Ensure to have set DIP 3 to ON.
Button K BUTTON always inserted in automatic functioning mode (DIP 6 OFF).
Replace button or switch of the selector switch.
Failed edge self-test => check the connections between electronic board and edge feeder.
Attention: if not using a feeder for edges, DIP 10 must be set OFF.
Faulty safety edge contact.
Faulty photocells contact with DIP 4 OFF.
Fix or replace the relative contact.
Impulse K always inserted.
Check and replace any buttons or micro-switches of the selector switch.
19
SOLUTION
G
B