Ribind J Importantes Instrucciones De Seguridad Para La Instalación página 18

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

G
B
5 - Re-set DIP 1 to OFF and DIP 2 to OFF.
RADIO CODES CANCELLATION PROCEDURE
The position of the door does not affetc the code memorisation.
1 - Set DIP 1 to ON and subsequently DIP 2 to ON => DL1 programming led will lighten with a
frequency of 1 s ON and 1 s OFF for 10 s.
2 - During the 10 s => press and keep pressed the PROG. Button for 6 seconds => the memory
cancellation is signalled by two flashings of the DL2 green Led.
3 - Subsequently DL1 programming led stays active and it is possible to add new codes
following the procedures described above.
4 - Re-set DIP 1 to OFF and DIP 2 to OFF.
MEMORY SATURATION SIGNALING
The position of the door does not affect the code memorisation.
1 - By setting DIP 1 to ON and subsequently DIP 2 to ON.
2 - DL2 green Led lightens for 6 times thus signalling that the memory is full (60 codes
available).
3 - Subsequently the DL1 programming led stays active for 10 s, thus enabling the possible
total cancellation of the codes.
4 - Re-set DIP 1 to OFF and DIP 2 to OFF.
OPERATION OF THE OPERATING ACCESSORIES
ATTENTION: ONLY IMPULSIVE COMMANDS HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors) used on the
installation are set in the IMPULSIVE mode, otherwise, the rolling shutter will be operated
even without the protection of the safety devices.
OPERATION BUTTON (COM-K BUTTON)
DIP 6 ON => It cyclically commands open-stop-close-stop-open-etc.
DIP 6 OFF => It opens the door when this is closed. If it is operated while the door is opening, it
has no effect. If it is operated when the door is open, it closes the door and, if it is
operated while the door Is closing, it opens the door again.
CLOCK FUNCTION
If you want the Clock Function must request J with firmware 02.
ATTENTION: A CLOCK CONNECTED TO J with fw 03 or more ACTIVATES THE AUTOMATIC
MOVEMENT OF THE AUTOMATION WITHOUT HAVING THE PROTECTION OF THE SAFETY DEVICES!
The Clock Function is useful In the rush hours, when vehicle traffic is slow (e.g. entry/exit of
workers, emergencies In residential or parking areas and, temporary, for removals).
CLOCK FUNCTION APPLICATION
It is necessary to request a J control panel with firmware 02.
Select the automatic functioning DIP 6 OFF.
By connecting a switch and/or a daily/weekly timer (in place or in parallel with the opening
button N.O. "COM-K BUTTON"), it is possible to open the automation or to keep It open, as long
as the switch is on or the timer is activated.
When the automation is open, all operating functions are inhibited.
On switch release, or at set time, the actuator will close.
RADIO TRANSMITTER
DIP 6 ON => It cyclically commands open-stop-close-stop-open-etc.
DIP 6 OFF => It opens the door when this is closed. If it is operated while the door is opening,
it has no effect. If it is operated when the door is open, it closes. If it is operated
while the door is closing, it opens the door again.
SAFETY ACCESSORIES OPERATION
PHOTOCELL (COM-PHOT.) - Safety function PL "b" according to EN13849-1
DIP 4 OFF => The door does not open if there is an obstacle within the photocells range of action.
During operation, photocells work both when the door opens (by starting the
opening movement again after half a second time), and when it closes (by starting
the reverse movement after one second time).
DIP 4 ON => If there is an obstacle within the photocells range of action when the door is closed
and its opening is commanded, the door opens (during its opening, photocells do
not work). Photocells work only while the door is closing (by starting its reverse
motion after one second, even if they are still engaged).
NOTE: in case this line is not used, bridge the contacts COM-PHOT.
SAFETY STRIP (EDGE - COM) - Safety function PL "b" according to EN13849-1
During the opening it's not active.
During the closure, if committed, reverses the opening movement.
If during the closing acts for a second time, running a small reversion of 1 second and signals
the alarm of fails or involved safety strip (contact NO).
If the safety strip is engaged (NO contact), the movement is allowed only with man present (see
section FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING).
In case the safety strip is not installed, this contact must be short circuited with a wire jump
(from EDGE to COM) to permit the shutter to operate.
PAY ATTENTION: it is highly recommended to check safety-strips operation at least every 6
months.
SAFETY STRIP ALLARM
If after the first safety strip obstacle detection, the safety strip is released
and then engaged again before the end of the shutter travelling, the shutter interrupts any
movement and this alarm state will be signalled by the Blinker or by the courtesy light for 1
minute together with DL1 programming light that will blink every 4 seconds.
The normal shutter operations can be restored by pressing any push button or radio commands.
TESTING THE SAFETY STRIP equipment (DIP 7 ON)
The DIP 7 ON enables the Test of safety strip equipment.
The Test is performed every time the shutter completes a full opening.
It is suitable only if the safety strip device is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input has to be connected to the A+TEST and
A- outputs (DIP 7 ON).
Automatically, every time the shutter completes a full opening, just before closing, the control
board switches OFF the A+TEST and A- power supply output for a very short time.
While the safety strip power supply is switched OFF, if everything is working fine the safety
strip contact (EDGE - COM) must open.
In case the test fails, no other gate manoeuvre will be allowed and the alarm state will be
signalled by the blinker or by the courtesy light that will remain on.
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH DIP 7 MUST BE LEFT OFF.
MODE "WORK ALWAYS" IN CASE OF FAILURE OF ONE OF THE SAFETY DEVICES.
If the safety edge fails or remains engaged for more than 5 s, or if photocell fails or remain
engaded for more than 60 seconds, the K BUTTON command will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the programming led.
With the blinking of the programming led, the opening and closing operation are allowed only
with the command button pressed and held.
The radio commands and that of automatic closing, will be excluded, since their use in this
mode, is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard commands
that were selected, such as step by step, automatic mode, radio commands and automatic
closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety strips (or
photocells) the photocells (or safety strips) still work by interrupting the operation
in progress.
The dead-man operation is only an emergency operation which must be activated for a very
short period and with the complete installation at sight so to have a secure and safe control
of the system.
As soon as possible however, the failing safety devices must be repaired and activated.
BLINKER AND/OR FLASHING LIGHT (DIP 5)
DIP 5 ON => it is possible to connect a flasher
N.B.: This electric board can supply power ONLY TO BLINKERS WITH (ACG7072) BLINKING
CIRCUIT, with max. 40 W lamps.
DIP 5 OFF => it is possible to connect a lamp for garage lighting (40 W max).
On every command input, the courtesy lamp will lit for 2 minutes. If during the 2 minutes time, a
second input is generated, the time elapsing will automatically restart for 2 minutes.
PRE-FLASHING FUNCTION
DIP 8 OFF => the FLASHING LIGHT and the motor will start at the same time.
DIP 8 ON => the FLASHING LIGHT starts working 3 seconds before every movement of the motor.
AUTOMATIC CLOSING (DIP 3 ON)
The pausing time before the automatic closing is set during the "Time Programming".
In this case the maximum pausing time available is 5 minutes.
DIP 3 ON (enabled).
RESTORING OF OPERATION FOLLOWING A POWER SHUT OFF
In case of power shut off the fence stops and the control unit will keep memory of the
interrupted motion.
18
Tabla de contenido
loading

Este manual también es adecuado para:

J-crxAc07081Abj7080Abj7079Ac07080Ba03224

Tabla de contenido