Adjustment Data - Ecoflam MAXFLAM D 10 Manual Del Usuario

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 38
420010404000 Maxflam D 10-20
EN
- At the end of the prepurging, the control box shut off the solenoid valve "O" while opening the 1st stage
valve (for example valve "A"), allowing the burner ignition in Low Flame.
- In order to have a correct combustion, adjust the combustion air flow (see figure).
- The fuel pressure during burner's working shall be set to 23 bars.
ADJUSTEMENT OF PRESSURE IN PREPURGING PHASE
NOZZLE
gph
spry
1.00
60°HO
1.25
60°HO
1.50
60°HO
2.00
60°HO
1.50
60°HO
2.00
60°HO
2.50
60°HO
3.00
60°HO
L

ADJUSTMENT DATA

PUMP
OUTPUT
bar
kg/h
23
6
23
8
23
9,5
21
12
23
9,5
23
12,50
23
15,80
23
20
AIR REGULATION SUCTION SIDE
FIRING HEAD SETTING
1 2 3
FIRING HEAD SETTING
Pos.
1
1
1
2
1
2
2
3
- 22 -
AIR DAMPER ADJUSTMENT
Pos.
2,20
2,80
3,50
4,50
3,50
4,50
5,50
8
Tabla de contenido
loading

Este manual también es adecuado para:

Maxflam d 20

Tabla de contenido