Alarms And Faults - Roger Technology CTRL/P Instrucciones Y Advertencias Para El Instalador

Centrale di comando per barriere elettromeccaniche versione per parcheggi
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 141
16

Alarms and faults

PROBLEM
ALARM SIGNAL
POWER LED off
POWER LED off
The barrier does
not
open
or
close.
Example:
flashing
76
POSSIBLE CAUSE
No power.
Fuses blown.
Fuse F1 blown or damaged.
This message is not visible if controller
is in battery power mode.
Input mains power voltage fault.
Controller initialisation failed.
Overcurrent detected in inverter.
Incorrect connection between SEC1
and SEC2 of the transformer.
Travel data acquisition error.
Calibration procedure failed.
Automation system position selection
modification message with parameter
.
Motor not connected.
BreakAway system alarm.
Configuration parameter error.
Release device open.
Open barrier inspection hatch (if the
emergency stop micro-switch is in-
stalled).
LOCKS connectors incorrectly con-
nected.
STOP button/contact active for more
than 5 s.
Encoder 1 not connected.
CORRECTIVE ACTION
Check power cable.
Replace fuse. Always disconnect from mains power
before removing and refitting fuses.
Replace fuse. Always disconnect from mains power
before removing and refitting fuses.
Disconnect from mains power, wait 10 seconds then
reconnect to the mains and switch on.
We recommend replacing the control unit if the problem
persists.
Press the TEST button twice or perform 3 command
requests in succession.
Swap the connection between SEC1 and SEC2.
Check that the spring is balanced correctly with the
barrier unlocked.
Press TEST and check if any safety devices are in alarm
state.
Repeat acquisition procedure.
Allow the indicated calibration times to elapse during
self-acquisition.
Check that
is shown flashing on the display befo-
re closing the release lock cover.
Repeat acquisition procedure.
SX
Motors for barriers are factory configured for right hand
opening barriers
(position of barrier relative to
passage seen from inspection hatch side). If the posi-
tion is changed and message
• Move the boom 45° degree.
• Adjust the spring position correctly for the required
opening direction.
• Disconnect from mains power or remove the main
fuse and wait 5 seconds.
• Reconnect to mains power or refit the fuse.
• Press and hold PROG until
appears on the display.
Repeat acquisition procedure.
Check the motor cable.
• Check the setting of par.
.
• Check the correct ACS/BA/60 system connection
to the control unit.
• Re-engage the boom.
• Consider replacing the boom if it is damaged.
Set configuration value correctly and save.
Lock by turning the key two complete turns clockwise.
Close the inspection hatch correctly and check the
micro-switch connection.
Check the connector connections.
Jumper one of the two LOCKS connectors.
Check connections to STOP button.
Check connection to encoder. Replacing the encoder is
recommended if the problem persists.
DX
is displayed:
disappears and