SMA Solar Technology AG
igure 28: LCS-Tool - setting Time of Use
Procedure:
1. Open the LCS-Tool.
2. Log in as an Installer.
3. Call up the menu Setup.
4. In the Inverter Parameter menu in the
Immediate controls area, ensure that the
parameter Active Power (P_ref) is set to
100%.
5. Ensure that the Modbus parameter 40349
(WMaxLimPct) is set to 100%.
6. In the Power Management menu, enable the
Time of Use function. Otherwise, the Peak
Load Shaving function might be used.
Installation Manual
7. To defne the time windows of both periods,
under Seasons select the period to be defned
and adjust the corresponding settings: To
defne the entire day with the same setting,
select All Day feld of the corresponding
weekday. The same setting is valid for the
power throughout the day. To make settings for
the individual periods, select the desired
periods of the corresponding weekday.
8. Under Seasons select the period to be used.
9. Enter the power of the respective time interval.
As a result, the battery is discharged ( eed in),
if needed, at values with a positive sign (+),
and charged (Charge) at values with a
negative sign (-).
10. Select [Save] to save the changes.
IMVIOBOX-IA-xx-18
5  LCS-Tool
39