BACKLASH TIME

To avoid that the gate starts the opening phase
before the electrical locks is unhooked, it is possible
to introduce a time of inversion adjustable from 0 to
120 seconds (± 0,5). In this way during the opening
phase, the gate inverts the motion through the set
time permitting the unhooking of the electrical lock.

PRE-FLASHING TIME

This menu permits the introduction of a pre-flashing
that occurs before any movement of the gate either
in opening or in closing phase: the time of
pre-flashing can be adjusted from 0 to 120 seconds
(± 0,5).
SLOWING DOWN TIME (Pd5 only)
This menu permits the activation of the gate slowing
down function for a time to be set between 0 and
120 s(± 1,5 s). To set the slowing down function
proceed as follows: leave a slowing down time at 0
and make sure that the gate opens and closes
correctly. After that, set the slowing down time (for
ex. 5 or 6 s).
FAST CLOSING TIME AFTER SLOWING DOWN
DURING CLOSING (Pd5 only)
When a slowing down time different from 0 s is set,
it is possible that the gate speed is not sufficient to
trigger the lock during closing. For this reason, after
the end of the slowing down phase, it is possible to
close the gate at a normal speed (without slowing
down) for a time to be set between 0 and 120 s
(± 0,5).