Danfoss TLX 6k Serie Manual Del Usuario página 9

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 59
3.
Type the applicable output limit of the inverter (for example 70%).
4.
Click "Save".
For example:
When the installed power is 18 kWp, and the output power of the inverter is limited to 70%,
then output power = 18 x 0.7 = 12.6 kW.
To set a percentage based on nominal AC output power:
Go to [Inverter → Setup → Grid management → Output power].
1.
2.
Click on "Percentage based on nominal AC output power".
3.
Type the applicable output limit of the inverter (for example 70%).
4.
Click "Save".
The inverter output power will now be limited to a percentage of the nominal AC output power.
For example:
For a 12.5 kW inverter when the output power is limited to 70%, then output power = 12.5 x
0.7 = 8.75 kW.
3.4. Verification
To verify that the change in configuration has been implemented, access at security level 0 or
higher is required.
3.4.1. Display Interface (Inverter Level)
To view the output power limit of the inverter
Go to [Status → Grid management → Output power limit]
The value of the limit is displayed as an absolute value or percentage, depending on
the chosen setting.
3.4.2. Web Server or Service Interface (Plant Level)
To view the power level adjustment setting of the plant
Go to [Plant → View → Overview].
The value for power level adjustment of the plant is displayed as a percentage.
3.4.3. Web Server or Service Interface (Inverter Level)
To view the overall output power limit of the inverter
Go to [Inverter → View → Overview].
The value for power level adjustment of the inverter is displayed as a percentage.
To view the output power limit of the inverter
Go to [Inverter → Status → Grid management → Output power limit]
The value of the power limit is displayed as an absolute value or percentage, depend-
ing on the chosen settings.
3. Functionality Supporting EEG2012 (Ger-
L00410591-04_4z
many)
3
9