Electrical connections
5.2.2
Cable with part number D173D031U01
Prepare both cable ends as shown.
IMPORTANT (NOTE)
Use wire end sleeves.
•
Wire end sleeves 0.75 mm
•
Wire end sleeves 0.5 mm
The shields may not touch (signal short circuit).
25 (0.98)
1
2
3
4
5
6
7
8
9
Fig. 28: Flowmeter sensor side, dimensions in mm (inch)
1 Measurement potential 3, green
2 Signal line E1, violet
3 Shield 1S
4 Shield 2S
5 Signal line, E2, blue
6 Data line, D2, yellow
7 Data line, D1, orange
30 - EN
2
Flowmeter sensor side
"X"
8 (0.31)
13
L
2
X
10 11 12
Transmitter side
L2 = 70 (2.76)
L2 = 60 (2.36)
L2 = 60 (2.36)
L2 = 60 (2.36)
L2 = 60 (2.36)
L2 = 70 (2.76)
L2 = 70 (2.76)
FEX300, FEX500
2
(AWG 19), for shielding (1S, 2S)
(AWG 20), for all other wires
70 (2.76)
12 11 10
8 (0.31)
13
8 Magnet coil, M2, red
9 Magnet coil, M1, brown
10Foil shield (D1, D2)
11Foil shield continuity wire (D1, D2)
12Ground wire, steel
13SE clamp
X
1
2
3
4
5
6
7
8
9
"
" X
25 (0.98)
G01030-01
L2 = 90 (3.54)
L2 = 90 (3.54)
CI/FEX300/FEX500-X1