Input Specifications - Rockwell Automation MicroLogix 1200 Manual Del Usuario

Ocultar thumbs Ver también para MicroLogix 1200:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 75
18
MicroLogix™ 1200 Programmable Controllers
Description
Agency
• UL 508
Certification
• C-UL under CSA C22.2 no. 142
• Class I, Div. 2, Groups A, B, C, D
• CE compliant for all applicable directives
Electrical/EMC
The controller has passed testing at the following levels:
IEC1000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
IEC1000-4-3: 10V/m, 80 to 1000 MHz, 80% amplitude modulation, +900
MHz keyed carrier
IEC1000-4-4: 2 kV, 5 kHz; communications cable: 1 kV, 5 kHz
IEC1000-4-5: communications cable 1 kV galvanic gun
I/O: 2 kV CM (common mode), 1 kV DM (differential mode),
Power Supply: 4 kV CM (common mode), 2 kV DM (differential mode)
IEC1000-4-6: 10V, communications cable 3V
Terminal Screw
0.791 Nm (7 in-lb) rated
Torque

Input Specifications

Description
On-State Voltage
Range
Off-State Voltage
Range
Operating Frequency 47 Hz to 63 Hz
On-State Current:
Off-State Leakage
Current
Nominal Impedance 12K ohms at 50 Hz
Inrush Current (max.)
at 120V ac
1762-IN006A-ML-P
1762-L24AWA
1762-L24BWA
(UL 1604, C-UL under CSA C22.2 no. 213)
1762-L24AWA
1762-L40AWA
79 to 132V ac
0 to 20V ac
5.0 mA at
79V dc (min.)
12 mA at 120V dc
(nom.)
6.0 mA at
132V dc (max.)
2.5 mA max.
10K ohms at 60 Hz
250 mA
1762-L40AWA
1762-L24BWA and 1762-L40BWA
Inputs 0 through 3
14 to 26.4V dc at 55°C
(131°F)
14 to 30.0V dc at 30°C
(86°F)
0 to 5V dc
0 Hz to 20 kHz
2.5 mA at 14V dc
(min.)
8.8 mA at 24V dc
(nom.)
12.0 mA at 30V dc
(max.)
1.5 mA min.
2.5K ohms
Not Applicable
1762-L40BWA
Inputs 4 and higher
10 to 26.4V dc at 55°C
(131°F)
10 to 30.0V dc at 30°C
(86°F)
0 Hz to 1 kHz
(scan time dependent)
2.0 mA at 10V dc
(min.)
8.5 mA at 24V dc
(nom.)
12.0 mA at 30V dc
(max.)
2.6K ohms

Hide quick links: