7.4
Instalación conforme a UL
NOTA
El siguiente capítulo se imprime siempre en idioma inglés, independientemente del
idioma de esta documentación, debido a los requerimientos UL.
7.4.1
Power terminals
Use 75 °C copper wire only.
7.4.2
Short circuit current rating
•
•
Max. voltage is limited to 500 V.
7.4.3
Branch circuit protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For MOVIPRO
200 kA/500 V
When protected by:
Non Semiconduc-
tor Fuses (currents
Model
are maximum va-
PHC21A-
A022M1-...A-00/..
40 A/600 V
PHC21A-
A040M1-...A-00/..
40 A/600 V
PHC21A-
A075M1-...A-00/..
40 A/600 V
®
MOVIPRO
is suitable for use on a circuit capable of delivering not more than
200,000 rms symmetrical amperes when protected by fuses and circuit breakers
as described in the tables below.
®
MOVIPRO
is suitable for use on a circuit capable of delivering not more than
65,000 rms symmetrical amperes when protected by ABB and Rockwell Type E
Combination Motor controllers as described in the tables below.
®
use branch circuit protection as follows:
Three Phase 380 V – 500 V Voltage Range
SCCR:
SCCR:
200 kA/500 V
When protected by:
Inverse-Time Cir-
cuit Breaker
lues)
50 A max/500 V min
50 A max/500 V min
50 A max/500 V min
Instalación eléctrica
Instalación conforme a UL
SCCR: 65 kA/480 V
When protected
1)
by:
Type E Combinationen Motor Controller
ABB, Model
MS132‑6.3 Ra-
ted 480 V, 3 HP
ABB, Model
MS132‑10 Ra-
ted 480 V, 5 HP
ABB, Model
MS132‑16 Ra-
ted 480 V, 10 HP
Instrucciones de funcionamiento – MOVIPRO
7
SCCR: 65 kA/460 V
When protected by:
Rockwell Automa-
tion, Model
140M‑C2E-B63 Ra-
ted 460 V, 5 HP
Rockwell Automa-
tion, Model
140M‑C2E-C10 Ra-
ted 460 V, 7.5 HP
Rockwell Automa-
tion, Model
140M‑D8E-C16 Ra-
ted 460 V, 10 HP
59
®