Before You Begin
CAUTION: Risk of personal injury or product damage. If
the rain panel is not securely held in place during
installation, product may fall causing personal injury or
property damage. Get help when installing the light panel
assembly and waterways.
Observe all local plumbing, building, and electrical codes.
Read these instructions and determine all required components
along with their installation locations before beginning this
installation.
This product is designed for ceiling-mount installation only. Do
not install to a shower wall.
This manual covers vertical installation of the Power Data Supply
(PDS) in a service closet or 2x6 stud pocket. If the wall is
enclosed, an access panel must be provided for servicing.
The PDS may also be mounted under the floor joists. If mounting
under the floor, the unit must not be enclosed.
The PDS must be located within 25 ft (7.62 m) of the rain panel.
Inspect the supply piping for damage. Replace as necessary.
The PDS is intended for hardwire installation. Make sure
electrical power can be provided to a service closet or 2x6 stud
framing with access panel, not more than 2 ft (0.61 m) from the
intended PDS mounting location.
The installation must have a Class A Ground-Fault
Circuit-Interrupter (GFCI). The GFCI protects against
line-to-ground shock hazard. Use a 120 V, 20 A service.
To reduce the risk of electric shock, locate the PDS and overhead
rain panel within proximity to each other to allow for each cable
to have a drip loop.
Kohler Co. reserves the right to make revisions in the design of
products without notice, as specified in the Price Book.