Technical Specifications - Bosch FLM-420-O8I2-S Guia De Instalacion

Módulo de interconexión de ocho salidas con 2 entradas
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 16
15
en
Description
POWER
PI+ | PI-
IN OUT I
OUT I
PI+ | 4- to PI+ | 1-
OUT II
PII+ | 8- to PII+ | 5-
POWER
PII+ | PII-
IN OUT II

Technical specifications

LSN input voltage
Max. current consumption from LSN
Outputs
-
Max. switched voltage of outputs
-
Max. output current rating
-
External power supply
Inputs
1. Line monitoring with EOL:
-
EOL resistor
-
Overall line resistance R
(R
= R
+ R
+ R
Σ
L/2
L/2
2. Contact monitoring:
-
Max. current strength (current pulse)
Minimum activation time of the inputs IN 1 - 2
Maximum cable length of all inputs and outputs
which are connected to the loop or stub and not
electrically isolated from LSN
Permissible wire diameter
Permissible operating temperature
Permissible storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Classes of equipment as per IEC 60950
Housing material and color
Dimensions (W x H x D)
F.01U.032.849 | 2.0 | 2010.11
Function
Power supply output 1 to 4
Reference potential (PI+), switched negative potential output 1 to 4
Reference potential (PI+), switched negative potential output 5 to 8
Power supply output 5 to 8
Σ
)
EOL
15 to 33 V DC
5,5 mA
8, independent
30 V DC
700 mA per output (depending on external power supply)
5 to 30 V DC
2, independent
Nominal 3,9 kΩ
In standby: 1500 Ω - 6000 Ω
-
Short-circuit: < 800 Ω
-
Interruption: > 12000 Ω
-
8 mA
3,2 s
500 m in total
2
0.6 to 3.3 mm
-20 °C to +65 °C
-25 °C to +80 °C
<96 %, non-condensing
IP 54
Class III equipment
ABS+PC-FR, signal white (RAL 9003)
Approx. 140 mm x 200 mm x 48 mm
FLM-420-O8I2-S
Bosch Sicherheitssysteme GmbH
Tabla de contenido
loading