DIP-SWITCH SETTINGS
Turn off the power to the unit. This operation should be carried
out in the installation phase, by suitably trained and qualified
personnel only.
They can be used to obtain the following functions:
Position
Dip 1 (Default OFF)
OFF
ON
Dip 2 (Default OFF)
OFF
ON
Dip 3 (Default OFF)
OFF
ON
Dip 4 (Default OFF)
OFF
ON
Dip 5 (Default OFF)
OFF
ON
Dip 6 (Default OFF)
OFF
ON
Dip 7 (Default OFF)
OFF
ON
Dip 8 (Default OFF)
ON
OFF
Dip 6
Dip 5
Dip6
Dip5
OFF
OFF
OFF
ON
ON
OFF
ON
ON
SOME EXAMPLES:
VMF_E18 (default)
ON
ON
ON
OFF
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
ON
ON
OFF
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
22
Functions
Check water valve
No shut-off valve
Shutoff valve present
Position water temperature sensor :
Water temperature sensor downstream from shutoff valve
Water temperature sensor upstream from shutoff valve
Ventilation control:
Thermostat-controlled ventilation
Continuous ventilation
Ventilation enabling:
Enabling normal band
Enabling reduced band
** System type selection (See table)
Combinations between Dip 5 and Dip 6
** System type selection (See table)
Combinations between Dip 5 and Dip 6
Dead band:
Dead band 5°C
Dead band 2°C
Microswitch dedicated settings:
Microswitch used as thermostat season change
Microswitch used as thermostat housing
**SYSTEM TYPES
System type
System 2 Tubes with Electrical Resistance
System 4 tubes
System 2 Tubes with Plasmacluster / Bactericidal Lamp
System 2 Tubes (cold only) + Resistance (only hot)
ON
ON
OFF
OFF
SW
SW
ON
ON
OFF
OFF
SW
SW
AVMFE18LJ1701 - 6795748_02
* With shutoff valve
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW
SW
DUALJET
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW
SW
* Water sensor upstream from the valve
ON
ON
ON
OFF
OFF
1 2 3 4 5 6 7 8
ON
ON
ON
OFF
OFF
1 2 3 4 5 6 7 8
ON
OFF
SW
ON
OFF
SW