DSMI−...−B
Electrical installation
Note
Leakage currents can impair the measuring system.
S Make sure that the earth connection 6 is connected with the earth potential
(earth cable optionally either with eyelet or blade connector).
The cable cross section of the earth cable must be at least 2.5 mm
cable length must not exceed 0.5 m.
Insert the supplied screw aC with cutting
S
thread into the hole for the earth connec
tion 6.
This will ensure the electrical contact in
spite of the anodising layer.
Connect the measuring system to the
S
connecting cable as described in the des
cription of the positioning controller.
The PIN assignment is shown in the table below:
Pin
Designation
1
DC +10 V
2
Signal
3
GND
4
Screen
Fig. 20
For querying the end positions:
Place the proximity switch (B) SME/
S
SMT−10F−...−KL on the groove of the shock
absorber retainer.
A sensor bracket (è Accessories) is
required to fasten the proximity switch.
The proximity switch is actuated by
magnets (C) in the stop lever.
Festo DSMI−...−B 0806NH English
6
Fig. 19
Assignment
3
2
2
(B)
Fig. 21
2
and the
aC
1
4
4
(C)
33