Trouble Shooting Hints - Eaton SURE-LITES EUX Instrucciones De Instalación

Batería de respaldo con autodiagnóstico
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Cover Plate
Adapter
Plate
Figure 8
4. Remove the screws securing the trim plate to the
housing (See Figure 1). Place the trim assembly and
screws aside and save them for later installation.
It is not necessary to disconnect the wire harness
connecting the charger driver circuit board to the LED
board. Instead, the trim plate can be hung from the
sliding plastic installation hook (See Figure 2).
Secure the canopy to the junction box using the
adapter plate and screws provided (See Figure 7/8).
The adapter plate is designed to be connected to a
NEMA standard 3.5" round, 4" round, 3.5" octagon,
4" octagon, or handy (single gang) box. However,
it is possible to connect the adapter plate to other
electrical boxes with some modification.
5. Connect power supply and ground in accordance with
NEC and local codes. Wire connections are as follows:
Ground to Green Lead, Neutral to White Lead, 277V
line to Orange Lead (if used), 120V line to Black Lead
(if used). Cap unused Line Lead. (See Schematic)
6. Excess wire length can be held in place in the wire
trap (See Figure 5).
7. If the fixture is to be wall mounted, first, loosen the set
screw on the back of the pivot housing. Then remove
the locking clip by sliding it to the end of the pivot
housing (See Figure 5). Rotate the pivot housing 90
degrees, and then replace the locking clip. Tighten the
set screw.
8. Remove the trim assembly from the installation hook.
9. Replace the screws holding the trim assembly to the
housing.
10. Lens is provided in a separate box. Apply chevrons
and background as needed. Snap lens into place.
Orange Lead - to 277V
Black Lead - to 120V
White Lead - To Neutral
c
W7 W8
LED11
CN1
Instructions d'installation pour enseigne de sortie à éclairage périphérique universelle EUX - Pile de secours avec autodiagnostics
Housing
Guide
Bracket
Canopy
+
LED PCB
LED7
LED8
049-241
ADX141174
Installation Instructions for the EUX Universal Edge Lit Exit –
NOTE: If using the lens with the default transparent
background (instead of the provided white or mirror
backgrounds) it must be installed only where there is
adequate color contrast between the sign legend and
the interior wall finish behind the sign, to provide for
sufficient visibility.
11. Turn on power to fixture. Remove EZ Key battery
disconnect.
ACTIVATING OPTIONAL FEATURES
FLASHER: If the consumer desires the exit sign to flash
on and off when in emergency mode, remove the jumper
labeled FLASHER from the circuit board while unit is
de-powered. See Schematic.
MAINTENANCE: None required. Replace the batteries
as needed according to ambient conditions. Equipment
should be tested every 30 days in accordance with local
codes.
NOTE: Servicing of any parts should be performed by
qualified personnel. Only use replacement parts supplied
by Cooper Lighting. Use of unauthorized parts may void
the warranty.
CAUTION: This equipment is furnished with a
sophisticated low voltage battery dropout circuit to
protect the battery from over discharge after its useful
output has been used. Allow 24 hours recharge time
after installation or power failure prior to 90 minute
testing.

TROUBLE SHOOTING HINTS:

If LED display or charge indicator LED does not
illuminate, check the following:
1. Check AC supply – verify that unit has 24 hour AC
supply.
2. Unit is shorted or battery is not connected.
3. Battery discharged. Permit unit to charge for 24 hours
and then re-test.
4. If following the above trouble shooting hints does not
solve your problem, contact your local Cooper Lighting
representative for assistance.
SCHEMATIC: Voltages and wire colors may vary for
international versions. Check wire tags.
Pull Jumper Labeled "FLASHER" to Enable
Sign Flashing in Emergency Mode
c
041-1389
JP5
L1
FLASHER
J1
CN2 ICSP
REMOTE
F1
RMT-
Charger / Driver PCB
LED5
LED3
LED6
www.eaton.com
Battery Backup with Self Diagnostics
+
JP6
FAI
RMT+
+
CN4
Battery
CN3
LED1
LED4
LED2
JK1
3