Three-phase grid connection
PE N L3 L2 L1
Always use sufficiently dimensioned cable
cross-sections to prevent a significant incre-
ase of the grid impedance between the
service distribution system and the Solar
Inverter. The capacity of the AC terminals is
2
2
0.5 mm
to 6 mm
for rigid cables, and 0.5
2
2
mm
to 10 mm
for flexible cables. If the
grid impedance is high, i. e. due to relati-
vely long or thin cables, the voltage at the
grid terminal is increased during injection.
If the terminal voltage exceeds the admissi-
ble value, the Solar Inverter is disconnected
from the grid. If the power grid is weak
and the PV output is high, individual Solar
25 A
Inverters may repeatedly switch on and off.
Carry out the following steps carefully:
· Prior to inserting the power cable into
the device, make sure it is de-energised.