SELF-DIAGNOSIS FUNCTION

Indoor Unit Error
Ex) Error 03 (Remote controller error)
3 Times
LED02G
(GREEN)
Error Code
01
Indoor Room sensor error
02
Indoor in-pipe sensor error
03
Remote controller error
04
Drain pump error
05
Communication error indoor and outdoor
06
Indoor out-pipe sensor error
09
EEPROM error (indoor)
10
BLDC motor fan lock (indoor)
h Because remote controller turn off when occur ERROR in simultaneous operation system, it
should check LED blinks of outdoor in order to confirm error code.
h Repeatedly after LED1 is turned on and off as the Error code number of tens digit, LED2 is
turned on and off as the Error code number of single-digit.

DIP SWITCH SETTING

Function
SW3 Group Control
Dry Contact
SW4
Mode
SW5
Installation
3 Times
2 Sec.
2 Sec.
Description
Description
Selection of Master or
Slave
Selection of Dry Contact
Mode
Fan continuous operation
3 Times
LED 1(Red) LED 2(Green)
1time ◑
Setting Off
Master
Wired/Wireless remote
controller
Selection of Manual or
Auto operation Mode
Continuous operation
Removal
1time ◑
0
2times ◑
0
3times ◑
0
4times ◑
0
5times ◑
0
6times ◑
0
9times ◑
0
Indoor PCB
0
Indoor PCB
Indoor PCB
Indoor PCB
Setting On Default
Slave
Auto
Working
Indoor
status
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Off
Off
Off