ENGLISH
Finishing
1. Apply surrounding wall panels. Acceptable materials include fibre
cement, fire rated MDF, cement sheeting, stone cladding, tiles, steel,
and sheetrock.
Facing or finishing materials must never overhang into the appliance
opening.
WarninG! risk of Fire! do not apply combustible materials
beyond the minimum clearances. Comply with all minimum
clearances to combustibles as specified in this manual and the
burner manual.
iMPortant: a 155mm [6"] non combustible panel must be
installed above all sides of the appliance openings. see
examples below.
155mm [6''] MIN
Example: Single Sided Fireplace
Example: Peninsula Fireplace
2. A metal trim bead MUST be installed on all edges (mitre the corners).
(Do not use long fasteners thicker than the wall paneling material to
avoid penetrating the appliance).
www.ecosmartfire.com
3. Plaster all seams and beads.
All joints between the finished wall sheathing and the front of the
appliance must be sealed with non-combustible materials. Sealants,
such as caulk or mastic used to seal the gap between the wall and
the appliance, should be rated at a minimum continuous exposure to
150ºC (122ºF).
4. If desired finishing includes a painted wall, 100% acrylic latex or oil-
based or standard acrylics may be used. Follow paint manufacturer's
instructions for paint and primer application.
oPerate aCCordinG to the BUrner oPerations ManUal
inClUded With the BUrner.
ENGLISH
Mantel surrounds
Minimum Clearances
If the setting incorporates a mantel the minimum vertical and maximum
horizontal dimensions to combustible mantel identified in the image
below must be followed.
Finishing clearances to CoMBUstiBles
Ceiling
12.7mm [0.5''] Sheetrock
381mm [15''] MAX
914.4mm [36'' ]
12.7mm [0.5'']
Non-combustible board
330mm [13''] MIN
152.4mm [6''] Tall
Measurement is taken
from the top edge of the
Measurement is taken
from the bottom edge of the
50.8mm [2'' ] MIN
Floor or Shelf
12.7mm [0.5''] Sheetrock
Minimum vertical and maximum horizontal dimensions of
combustible mantel.
Finishing and clearances to non-CoMBUstiBles
Minimum vertical &
maximum horizontal
dimensions
101.6mm [4'']
50.8mm [2'']
2''
Measurement is taken
101.6mm [4'' ]
from the top edge of the
152.4mm [6'']
Floor or Shelf
Minimum vertical and maximum horizontal dimensions of
non-combustible mantel.
Warning! Risk of Fire! Comply with all minimum clearances
to combustibles as specified. Framing or finishing material
closer than the minimum listed must be constructed entirely
of non-combustible materials.
Decorative Box
Infill Plate
For appliances with a decorative side box, an infill plate is provided to lift
the material to align with the bottom edge of the appliance. Decorative
boxes must only be used to hold non-combustible accessories/materials.
Decorative Steel Logs are available as an optional accessory. Please
*Decorative logs must NOT be placed directly over an open flame. They
are designed to sit near heat but not over flames.
© Copyright 2004 - 2019 MAD Design Group. All rights reserved. V0719