Mechanical
• common probe/wetted parts: PPS process connection and PPS sensor; or 316L
process connection and PPS or PVDF sensor.
[Standard Metal process connection seal is FKM (e.g. Viton). FFKM (e.g. Kalrez) is optional].
• c c able version (SS process connection):
• integral cable body: 316L stainless steel
• 316L stainless steel process connection:
3/4" NPT or R 1" (BSPT), or G 1" (BSPP)
• e e nclosure version (SS process connection):
• housing: VALOX®(thermoplastic
polyester)
• lid: transparent thermoplastic
polycarbonate (PC)
• 316L stainless steel process connection:
3/4" NPT, or R 1" (BSPT), or G 1" (BSPP)
• e e nclosure version (fully synthetic process connection):
• housing: VALOX®(thermoplastic
polyester)
• lid: transparent thermoplastic
polycarbonate (PC)
• fully synthetic process connection:
3/4" NPT or R 1" (BSPT)
Process Conditions
• relative dielectric constant (Hr: 1.5 minimum
• temperature:
• pressure (vessel):
Approvals
1
• CE
• CSA
1
• ATEX
1
• C-TICK (Australia)
1.
Enclosure and cable stainless steel process connection versions only
Note: EMC testing was conducted on the CLS100 metal version while mounted in a
metallic vessel and wired using shielded cable. The sensitivity was set by turning
sensitivity potentiometer 2 turns counter-clockwise from the set point.
1.
®VALOX is a registered trademark of the General Electric Company.
7ML19985QJ83
• 1 m (3.3 ft) of 4 conductor, 22 AWG,
shielded, polyester jacket
1
• internal 5-point terminal block
• ½" NPT wiring entrance
(optional M20 x 1.5" cable entry)
• internal removable 5-point terminal
block
• ½" NPT wiring entrance
(optional M20 x 1.5" cable entry)
–30 to +100 °C (–22 to +212 °F) (enclosure version with
stainless steel process connection)
–10 to +100 °C (+14 to +212 °F) (enclosure version with
fully synthetic process connection)
–1 to 10 bar (146 psi) gauge, nominal
• FM
• WHG overfill protection (Germany)
• Lloyd's Register of Shipping, categories ENV1,
ENV2, and ENV5
Pointek CLS100 – QUICK START MANUAL
1
1
Page EN-3