With the burner switched off, connect a DC microammeter with a 0÷50 or 0÷100 µA dial. When the burner is run-
ning, and is properly adjusted, the value read must be steady and never be smaller than 1,5 µA (LME 11/21/22) .
1
4
FLAME DETECTION SYSTEM CHECK
min. 1,5 µA
POSITION OF ELECTRODES
A
IONIZATION
PROBE
REMOVING FIRING HEAD
2
5
420010563501 Max Gas 350 - 500 P/P AB
1
LANDIS
LME11/LME21-22
A
IGNITION
ELECTRODE
3
6
23
EN