SEZIONE B-
B
CHANGE BURNER OPERATION FROM NATURAL GAS TO LPG
In order to change the burner operation from natural gas to LPG you have to follow these instructions :
- Remove the blast tube. - Remove the ignition electrode. - Replace 4 Diffusers with LPG version, remove A screws. -
Remove the disc. - Replace Tooth with LPG version. - Install the disc and ignition electrode correctly. - Replace the
blast tube with LPG version.

POSITION OF ELECTRODES

Ignition electrode
B
A
15
A
Ionization probe
B
A
420010329303 Blu 1500.1 P AB