Fault
The flame goes out
directly after ignition.
Bio Energy series
Cause
6
The pump thermostat
has not reached the
right temperature yet.
7
The hot air thermostat is
defective.
8
The combustion air fan
is not functioning.
9
There is insufficient sup-
ply of combustion air
10 There is no proper flue
draught.
11
The flue draught is too
high or irregular.
12 The flue draught is too
low.
40.020.944 - rev. 05 - 2015
Solution
Let the heater cool down.
Restart the heater.
Let the heater burn longer
with the switch on "1", see
fig. 5 (A).
Replace the pump thermo-
stat.
Replace the hot air thermo-
stat.
Check the motor and replace
if necessary.
Clean the holes in the vapor-
iser, see fig. 4 (D).
Check the functioning of the
combustion air fan.
Check whether the flue is fit-
ted according to the descrip-
tion, see "flue".
Check the flue for leakage.
Clean the flue if necessary.
Position a flue stack valve,
see "flue".
Adjust the flue to the right
draught (see maintenance
table 5.1) with the counter-
weight on the valve (fig. 7)
Check all connections in the
flue.
Reduce the number of
bends.
Heighten the flue.
Isolate the flue outside the
building.
Check the flue, see "flue".
English
Action
User
User
Dealer
Dealer
Dealer
User
Dealer
User
User
User
Dealer
User
User
User
User
User
25