Holding register
Name
(Protocol)
40141
Acknowledge
(140)
40142
Alarm history index
(141)
40143
Alarm history error
(142)
code
State float swiches
40198
(197)
40204
Set points water
(203)
level 1
40205
Set points water
(204)
level 2
40206
Set points water
(205)
level 3
40212
Set points water
(211)
level 1
40213
Set points water
(212)
level 2
40214
Set points water
(213)
level 3
40220
Dry run level
(219)
40222
High water level
(221)
Manual de Instalação e funcionamento Wilo-Control EC-L
Anexo
Data type
Scale & unit
BOOL
UINT16
UINT16
0.1
BITMAP
UNIT16
1 cm
UNIT16
1 cm
UNIT16
1 cm
UNIT16
1 cm
UNIT16
1 cm
UNIT16
1 cm
UNIT16
1 cm
UNIT16
1 cm
Elements
Access
16: Priority off
17: Redundancy
18: Plausibility
19: Slave
communication
20: Net supply
21: Leakage
W
RW
R
0: DR
R
1: Ps off
2: P1 on
3: P2 on
4: HW
RW
RW
RW
RW
RW
RW
RW
RW
pt
Added
31.000
31.000
31.000
31.102
31.102
31.102
31.102
31.102
31.102
31.102
31.102
31.102
157