Panasonic S-22MU1E5 Instrucciones De Instalación página 13

Acondicionador de aire con sistema vrf - para refrigerante r410a
Ocultar thumbs Ver también para S-22MU1E5:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 171
Pana_indoor_336012_Eng.indb 19
3-16. Increasing the Fan Speed
If external static pressure is too great (due to long extension
of ducts, for example), the air flow volume may drop too low at
each air outlet. This problem may be solved by increasing the
fan speed using the following procedure:
(1) Remove 4 screws on the electrical component box and
remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends) clamped
in the box.
(4) Securely connect the booster cable sockets between the
disconnected fan motor sockets in step 2 (Fig. 3-52).
Electrical component box
Booster cable
Fan
Booster cable
motor
Fan motor socket
(At shipment)
(Booster cable installed)
(5) Place the cable neatly in the box and reinstall the cover
plate.
Indoor Fan Performance
73, 90 Type
150
15
10
100
HT
H
5
50
M
L
0
0
10
20
Air Flow (m³/minute)
HT: Using the booster cable
NOTE
H: At shipment
■ How to read the diagram
The vertical axis is the external static pressure (Pa) while the horizontal axis represents the air flow (m
curves for "HT", "H", "M" and "L" fan speed control are shown. The nameplate values are shown based on the "H" air flow. For the
3
73 type, the air flow is 18 m
/minute, while the external static pressure is 49 Pa at "H" position. If external static pressure is too great
(due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by
increasing the fan speed as explained above.
22, 28, 36 Type
45, 56 Type
150
15
150
100
10
100
Fig. 3-52
HT
5
50
50
H
M
L
L
0
0
0
5
10
10
Air Flow (m³/minute)
Air Flow (m³/minute)
106 Type
140, 160 Type
15
150
150
HT
100
10
100
H
5
50
50
M
L
L
0
0
0
20
30
20
30
Air Flow (m³/minute)
Air Flow (m³/minute)
3
/minute). The characteristic
21
2011/01/12 13:55:51
Pana_indoor_336012_Eng.indb 20
■ Slim Low Static Ducted Type (M1 Type)
3-17. Required Minimum Space for Installation and
Service
● This air conditioner is usually installed above the ceiling so
that the indoor unit and ducts are not visible. Only the air
intake and air outlet ports are visible from below.
● The minimum space for installation and service is shown in
the diagram. (Fig. 3-54)
● *H dimension means the minimum height of the unit.
● Select the *H dimension such that a downward slope of at
least 1/100 is ensured as indicated in "3-22. Installing the
Drain Pipe".
15
10
5
HT
H
● The diagram shows the detailed dimensions of the indoor
M
unit. (Fig. 3-55)
0
15
15
10
HT
H
5
M
0
23
40
15
Fig. 3-53
824(Suspension bolt pitch)
Min. 200
or more
Flange for air
outlet duct
Min. 100 mm or more for bottom air intake
640
564 (Suspension bolt pitch)
38
126
194
27
155
22
120
40
14
10
80 143
30
44
238
22
2011/01/12 13:55:51
Electrical
component box
Inspection
access
450x450
Refrigerant tubing
Min. 650 or more
Unit: mm
Min. 20 or more
Min. 20 or more
Ceiling
Fig. 3-54
Flange for air inlet duct
145
Fig. 3-55
Tabla de contenido
loading

Tabla de contenido