The ECONOMY MODE selection screen will appear.
ECONOMY MODE is a UPS setting that enables enhanced efficiency and reduced BTU output
by suspending double-conversion circuits whenever input power is already of sufficient
quality to run connected equipment. If enabled, the UPS will run in economy mode when the
voltage is within ±10% of nominal. If the voltage goes beyond the ±10% range, the UPS
returns to on-line mode.
ACCEPT AND ADVANCE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
6
The AUDIBLE ALARM selection screen will appear.
The AUDIBLE ALARM screen gives the user the ability to permanently enable or disable the
UPS's audible alarm in case of an alarm event. The factory configuration of ON is ideal for
most applications. Certain applications may require the alarm to be disabled, in which case
the option of OFF can be selected.
ACCEPT AND ADVANCE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
7
The OVERLOAD ALARM selection screen will appear.
OVERLOAD ALARM refers to the point at which the UPS will sound its' overload alarm. The factory
setting of 105% will provide adequate overload warnings for most applications, but alternative
values from 5% to the 105% default (in 5% intervals) are available for custom configurations.
ACCEPT AND ADVANCE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
13-03-138 93-3168-EN.indd 23
VIEW ALTERNATE SETTINGS
To VIEW ALTERNATE SETTINGS,
press
the
SETUP
repeatedly (under 1 second
each).
AVAILABLE VALUES
OFF (factory), ON
VIEW ALTERNATE SETTINGS
To VIEW ALTERNATE SETTINGS,
press
the
SETUP
repeatedly (under 1 second
each).
AVAILABLE VALUES
ON (factory), OFF
VIEW ALTERNATE SETTINGS
To VIEW ALTERNATE SETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
105% (factory), 95%, 85%,
75%, 65%, 55%, 45%, 35%,
25%, 15%, 5%
23
LEAVE UPS SETUP MODE
To leave UPS setup mode,
BUTTON
PRESS and HOLD the SETUP
BUTTON (about 3 seconds).
NOTE - the UPS must be in STANDBY MODE
to change the economy mode setting
LEAVE UPS SETUP MODE
To leave UPS setup mode,
BUTTON
PRESS and HOLD the SETUP
BUTTON (about 3 seconds).
LEAVE UPS SETUP MODE
To leave UPS setup mode,
PRESS and HOLD the SETUP
BUTTON (about 3 seconds).