Operation
2
The OUTPUT FREQUENCY selection screen will appear.
OUTPUT FREQUENCY refers to the cycles-per-second (Hz) of UPS output power. This value is
most commonly set to match the prevailing country or region-specific frequency. In general, in
the USA, Canada and Mexico use the 60Hz factory setting. In 100-127V 50Hz locations, such
as Jamaica, Antigua and parts of Japan, set the UPS to 50Hz. To successfully configure your
UPS to convert frequency from 50-to-60Hz or 60-to-50Hz, set BOTH the OUTPUT FREQUENCY
to the desired setting and enable this function by setting the FREQ CONVERSION to ENABLE.
ACCEPT AND ADVANCE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
3
The FREQUENCY CONVERTER selection screen will appear.
FREQUENCY CONVERTER refers to the ability of the UPS to convert 60Hz to 50Hz or 50Hz to
60Hz. The UPS system automatically selects 50 Hz or 60 Hz operation based on utility power
conditions at start-up. The factory configuration of OFF is ideal for most applications. Some
users may wish to convert frequency for connected equipment. To successfully configure your
UPS for frequency conversion, turn ON the FREQUENCY CONVERTER function and SET the
OUTPUT FREQUENCY function to the desired 50 or 60 Hz setting.
ACCEPT AND ADVANCE
To ACCEPT the current value
& ADVANCE to the next
configuration screen , press
the ON/SELECT button (less
than 1 second).
4
The BYPASS RANGE selection screen will appear.
BYPASS RANGE: Sets the allowable voltage deviation from nominal input voltage that is
acceptable for the unit to go to bypass in a fault condition. If the voltage goes outside the range,
the unit will not go to bypass. If the unit is already in bypass, it will turn the output off. The factory
setting of WIDE is compatible with the vast majority of networking equipment. Regardless of the
"plus or minus" value entered, the highest bypass voltage available is 135V. The lowest bypass
voltage available is 90V (full load) and 70V (<70% load). The "Wide" range reflects these same
values (full load 90 to 135V / <70% load 70 to 135V).
ACCEPT AND ADVANCE
To ACCEPT the current value
& ADVANCE to the next
configuration screen, press
the ON/SELECT button (less
than 1 second).
13-03-138 93-3168-EN.indd 22
VIEW ALTERNATE SETTINGS
To VIEW ALTERNATE SETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
60Hz (factory), 50Hz
VIEW ALTERNATE SETTINGS
To VIEW ALTERNATE SETTINGS,
press the SETUP BUTTON
repeatedly (under 1 second
each).
AVAILABLE VALUES
OFF(factory), ON
VIEW ALTERNATE SETTINGS
To VIEW ALTERNATE SETTINGS,
press
the
SETUP
repeatedly (under 1 second
each).
AVAILABLE VALUES
HI (factory), 5%, 6%, 7%, 8%,
9%, 10%, 11%, 12%, 13%,
14%, 15%
22
LEAVE UPS SETUP MODE
To
leave UPS setup mode,
PRESS and HOLD the SETUP
BUTTON (about 3 seconds).
NOTE - the UPS must be in STANDBY MODE
to change the output frequency setting
LEAVE UPS SETUP MODE
To
leave UPS setup mode,
PRESS and HOLD the SETUP
BUTTON (about 3 seconds).
NOTE - the UPS must be in STANDBY MODE
to change the frequency converter setting
LEAVE UPS SETUP MODE
To leave UPS setup mode,
BUTTON
PRESS and HOLD the SETUP
BUTTON (about 3 seconds).
3/28/2013 1:05:38 PM