FAULTS - TECHNICAL AFTER-SALES ASSISTANCE
EN
TECHNICAL ASSISTANCE
THE TEMPERATURE
IS NOT SUFFICIENTLY
LOW
THE COMPRESSOR
DOES NOT START
WORKING OR WORKS FOR
VERY SHORT PERIODS
Use and maintenance manual
GOURMET ∫ EXPO WINE
CAUSE
Internal ventilators
not working
or damaged fans
Thermostat /
Electronic control board
not efficient
Condensing unit blocked
with dust or dirt in general
Insufficient refrigerant
load in the cooling system
Maximum pressure switch
triggered
(if present)
82
SOLUTION
Replace the ventilators/fans.
Replace the thermostat/electronic control board.
If the electronic control board is used on appliances with R290
coolant, it must only be replaced with an original spare part
supplied by the manufacturer. Replace the temperature probes
only after having ascertained which of them is inefficient.
Clean the condensing unit thoroughly.
The condensing unit in particular operating environments
(e.g. presence of dust, presence of excessive humidity, etc.)
when the performance of the appliance deteriorates requires
careful cleaning.
Find the cause of the refrigerant loss and remove it;
top up the refrigerant load if necessary having emptied
the system.
Check the reasons why the pressure switch is operating at
maximum pressure levels, such as: air condenser obstructed,
condenser fan with air stopped, ambient temperature too
high, pressure switch defective.
428001127000
2019-12