Fuel Selection Dial

The Fuel Selection Dial allows operation using
either gasoline (A) or LPG (B). Place the dial
in the 12 o'clock position (C) for long-term
storage. See
Figure
A
Figure 2-4. Dial Positions

Multimeter

The Multimeter tracks hours of operation for
scheduled maintenance. See
The Multimeter also displays Voltage Output,
Voltage Frequency, and Session Operation
Time. To change the display information,
press the MODE button.
Figure 2-5. Multimeter

Connection Plugs

120 VAC, 20 Amp, GFCI Duplex
Receptacle
The 120 Volt outlet is overload protected by a
20 Amp push-to-reset circuit breaker. See
ure
2-6. Each receptacle will power 120 Volt
AC, single phase, 60 Hz electrical loads
requiring up to 2400 watts (2.4 kW) or 20
Amps of current. Use only high quality, well-
insulated, 3-wire grounded cord sets rated for
125 Volts at 20 Amps (or greater). It also pro-
vides protection with a Ground Fault Circuit
Interrupter with a press to TEST and RESET
button.
NOTE: Limit length of extension cords to fif-
teen feet, or less, to prevent voltage drop and
overheating of wires.
6
2-4.
B
C
Figure
2-5.
Figure 2-6. 120 VAC, 20 Amp, GFCI Duplex
120 VAC, 30 Amp Receptacle
Use a NEMA TT-30R plug with this receptacle.
002609
Connect a suitable 3-wire cord set to the plug
and to desired load. The cord set should be
rated for 125 Volts AC at 30 Amps (or greater).
See
Figure
Use this receptacle to operate 120 Volt AC,
60Hz, single phase loads requiring up to 3600
watts (3.6kW) of power at 30 Amps. The outlet
is protected by a 30 Amp push-to-reset circuit
breaker.
002225
Figure 2-7. 120 VAC, 30 Amp Receptacle
120/240 VAC, 30 Amp Receptacle
Use a NEMA L14-30 plug with this receptacle
(rotate to lock/unlock). Connect a suitable 4-
wire grounded cord set to plug and desired
load. The cord set should be rated 250 Volts
AC at 30 Amps (or greater). See
Fig-
Use this receptacle to operate 120 Volt AC, 60
Hz, single phase loads requiring up to 3600
watts (3.6 kW) of power at 30 Amps or 240
Volt AC, 60 Hz, single phase loads requiring
up to 7200 watts (7.2 kW) of power at 30
Amps. The outlet is protected by one 30 Amp
2-pole circuit breaker.
Receptacle NEMA 5-20R
2-7.
NEMA TT-30R
Owner's Manual for Portable Generator
000203
002226
Figure
2-8.