AERMEC ANKI 020 Manual De Instrucciones página 29

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

N
Code
N39
N40
N41
N42
N43
N44
N45
N46
N47
N48
N49
N50
N51
12
Name
Min
Default Max
Minimum Volts
0.0
0.0
0-10V
Maximum Volts
0.0
10.0
0-10V
Min demand limit
0.0
0.0
value
Max demand limit
0.0
100.0
value
Min cold setpoint
-20.0
7.0
value
Max cold setpoint
-20.0
12.0
value
Min hot setpoint
-20.0
40.0
value
Max hot setpoint
-20.0
45.0
value
System storage
-20.0
45.0
tank SetPoint
System storage
0.0
5.0
tank band
Minimum
domestic hot
-50.0
0.0
water setpoint
offset
Maximum
domestic hot
-50.0
0.0
water setpoint
offset
Countdown to
next defrosting
Meaning
Minimum volts which must be matched by the final result in relation to
the configuration of the multi-function input.
10.0V
(see parameter N11)
Maximum volts which must be matched by the final result in relation to
the configuration of the multi-function input.
10.0V
(see parameter N11)
Minimum demand limit value which must be matched by the minimum
100.0%
value set for the multifunction input in relation to the type of analogue
input set.
Maximum demand limit value which must be matched by the maximum
100.0%
value of the multifunction input in relation to the type of analogue input
set.
Minimum cold setpoint value which must be matched by the minimum
80°C
value set for the multifunction input in relation to the type of analogue
input set.
Maximum cold setpoint value which must be matched by the minimum
80°C
value set for the multifunction input in relation to the type of analogue
input set.
Minimum hot setpoint value which must be matched by the minimum
80°C
value set for the multifunction input in relation to the type of analogue
input set.
Maximum hot setpoint value which must be matched by the minimum
80°C
value set for the multifunction input in relation to the type of analogue
input set.
Storage tank setpoint when multi-function input is configured as a remote
80°C
probe on the storage tank.
Adjustment band using remote probe on system storage tank when the
30.0
multi-function input is configured.
Minimum offset to be applied to the domestic hot water setpoint when
50.0
the function is configured through the multi-function input.
Maximum offset to be applied to the domestic hot water setpoint when
50.0
the function is configured through the multi-function input.
Read-only parameter.
Displays the time remaining to the start of the next defrosting. (if all other
defrosting conditions are met).