TECHNICAL CHARACTERISTICS
TECHNICAL DATA AND OPERATING RANGE DIAGRAM GAS XP60/2CE EVO
MODEL
Thermal power min. 1°st. / min. 2°st. - max. 2°st. *
Thermal power min. 1°st. / min. 2°st. - max. 2°st. *
Gas flow G20 (NATURAL GAS) min. 1°st. / min. 2°st. - max. 2°st. *
Gas flow G31 (L.P.G.) min. 1°st. / min. 2°st. - max. 2°st. *
Fuel: NATURAL GAS (second family) - L.P.G. (third family)
Fuel category:
Intermitted working operation (min. 1 stop every 24 hours) two stages
Environmental conditions operation / storage:
Max. temperature combustion air
Minimum pressure gas train D1"-S NATURAL GAS/L.P.G. **
Minimum pressure gas train D1"1/4-S NATURAL GAS/L.P.G. **
Minimum pressure gas train D1"1/2-S NATURAL GAS/L.P.G. **
Maximum pressure at the entry of valves (Pe. max)
Nominal electric power
Fan motor
Nominal motor current absorption
Nominal auxiliary absorption
Power supply:
Electric protection degree:
Noisiness *** min. - max.
Burner weight ****
* Reference conditions: Environment temperature 20°C - Barometric pressure 1013 mbars - Altitude 0 metre (sea level).
** Minimal feeding-gas pressure to the gas train to get the maximum power of the burner, considering counter-pressure in combustion chamber of
value 0 (zero).
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 metre of distance (UNI EN ISO 3746 -
Control method Class 3 - The tolerance on the measured sound pressure can be assumed equal to ± 1 [dB (A)]).
**** For burner with long head add 1 kg to the weight.
GAS XP60/2CE EVO
TECHNICAL CHARACTERISTICS
GAS XP60/2CE EVO
[Mcal/h]
100/200-542
[kW]
116/232-630
[Nm³/h]
11.6/23.3-63.3
[Nm³/h]
4.5/9-24.5
I2R,I2H,I2L,I2E,I2E+,I2Er,I2ELL,I2E(R)
I3B/P,I3+,I3P,I3B,I3R
-15...+40°C / -20...+70°C, umidità rel. max. 80%
[°C]
[mbar]
115.3 / 60
[mbar]
54.5 / 37.4
[mbar]
17.7 / 21.8
[mbar]
[W]
[W]
[A]
[A]
3~400V, 1N~230V - 50Hz
[dB(A)]
69-72
[kg]
GB
071011_2_A
60
360
700
550
1.4
0.5
IP 40
30.5
2