MAINTENANCE

EXTRACTION OF THE COMBUSTION HEAD

ATTENTION: REMOVE VOLTAGE!
D A N G E R
The combustion head can be taken out without removing the burner from the boiler:
a) Take-off the lid (2) by loosening the 3 screws.
b) Loosen the screw (1) with a 10mm fixed wrench
c) Take-out the head (3) by rotating it of 180°
d) Pull the ignition cables (RED)
e) Pull the probe cable (Black).
ATTENTION: During the reassembling be careful not to take the cables by mistake. (See section about POSITIONING
ELECTRODES).

ELECTRODES POSITIONING

LEGEND
1) 4mm: Flame Disk - probe distance *
2) 3mm: Ignition electrode-pivot distance
3) RED pipe
4) BLACK pipe
* ATTENTION: distance flame disk-probe of ionisation 12mm only mod.: GAS XP60/2CE EVO NATURAL GAS
GAS XP60/2CE EVO
MAINTENANCE
Fig. 15
Extraction of the combustion head
1
Fig. 16
Electrode positioning
3
4