14) Set Room Temperature
Point number: 13
Object name: SetRoomTemp_XXX (XXX: A/C unit address)
Object type: Analog Value
Meaning: This object is used to set the room temperature for the air conditioner.
Present_Value property:
Temperature(°C)
Remarks:
1. This unit is for indoor units only, and the approximate set temperature range is 18 ~ 35°C.
2. When COV registration is made, the COV will be reported the moment a temperature change
of at least
1°C is detected.

15) Room Temperature

Point number: 14
Object name: RoomTemp_XXX (XXX: A/C unit address)
Object type: Analog Input
Meaning: This object is used to monitor room temperature which the indoor unit is placed.
Present_Value property:
Temperature(°C)
Remarks: This object is for indoor units only, and reports the room temperature data measured
by the indoor units.
16) Alarm
Point number: 15
Object name: Alarm_XXX (XXX: A/C unit address)
Object type: Binary Input
Meaning: This object is used to monitor the Alarm.
Present_Value property:
ACTIVE: Alarm_On
INACTIVE: Alarm_Off

17) Error Code

Point number: 16
Object name: MalfunctionCode_XXX (XXX: A/C unit address)
Object type: Analog Input
Meaning: This object is used to monitor the details of the error status when the air conditioner
has an error.
Present_Value property:
Error code(Range is 0 to 255 )
Remarks: This object's error code descriptions should be referred to the corresponding table at
the "Reference LG original Error Code".