Objects (Modbus-Tcp); Supported Function Code - LG BNU-BAC Manual De Instalación

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 218

Objects (Modbus-TCP)

Objects (Modbus-TCP)

Supported Function Code

Monitoring and controlling items of air conditioners supported are assigned with general function
codes specified by Modbus-TCP.
Function Name
Read Coil Status
Read Holding Registers
Force Single Coil
Preset Single Registers
64 Modbus
Code
Run/Stop(status), Lock(status), Swing(status), Alarm, Filter
01h
Sign(status), Mode Lock(status), Wind Flow Lock(status)
Operation Mode(status), Fan Speed(status),
Room Temperature, Error Code,
Set Room Temperature(status),
03h
Set Lower Temperature(status),
Set Upper Temperature(status),
User Mode(status)
Run/Stop(setting), Lock(setting), Swing(setting),
05h
Filter Sign Reset, Mode Lock(setting),
Wind Flow Lock(setting)
Operation Mode(setting), Fan Speed(setting),
Set Room Temperature(setting),
06h
Set Lower Temperature(setting),
Set Upper Temperature(setting),
User Mode(setting)
Description
Tabla de contenido

Solución de problemas

loading

Tabla de contenido