Electrical Specifications
Input (RUN) Coil
Order No.
Coil Voltage
Isolation Voltage, V AC
Input Current, mA
On Voltage, volts min.
On Current, mA min.
Off Voltage, volts max.
Off Current, mA max.
Input Impedance, ohms (typical)
Table 6 : Input (RUN) Coil
User Outputs
User Output for 115 V AC and
230 V AC version
User Output for 24 V DC
version
Solid-State Outputs
Recommended
Fuse Type*
24
Rating
ISOL Logic to Power
Rating
On Voltage Drop
On Current
Off Leakage Current
ISOL Logic to Power
Rating
On Voltage Drop
Off Leakage Current
M (RUN)
Um = 100 %
FAULT
Two levels of short circuit protection can be provided by the user:
1.
Type 1 protection is available where the short circuit protective device protects the wiring and the
integrity enclosure. The soft starter will probably damage and require replacement or repair before
being re-energized. Circuit breakers and motor circuit protectors provide this type of protection.
2. Type 2 protection is available where the short circuit protective device protects both the wiring and the
soft starter. The soft starter should not require repair before re-energizing after the short circuit has been
cleared. Fuses of an KR-1 type or HRC-1 type sized in accordance with the NEC/CEC code or SITOR
semiconductor type fuses provide this kind of protection.
* For a complete listing of Siemens SITOR fuses, see Appendix A.
3RW34..0DC2.
..0DC3.
24 V DC
115 V AC
1500
1500
10
10
17 V DC
85 V AC
6
6
8 V DC
40 V AC
3
3
5 k
12 k
Outputs are rated 0.5 A maximum at 24 V DC, and 1.0 A at
115 V AC and 230 V AC.
1500 V AC
10 A Make
1 A Break
1 A Continuous at 115 V AC / 230 V AC
1.2 V AC (typical)
25 mA (minimum)
2 mA (typical)
1500 V AC
1.5 A Make
0.5 A Break
0.5 A Continuous at 24 V
1.6 V DC (typical)
2 mA (typical)
When soft starter is operating, the RUN contact is closed.
When motor is running at 100 % of line voltage (after starting is
complete), the Um contact is closed.
The FAULT contact responds either to an EEPROM error or to a
short-circuited thyristor, depending on the setting of switch
SW1-4.
(Refer to Section 7.1 re SW1-4 settings. Reset fault simply by
giving a new start signal.)
..0DC4.
230 V AC
1500
10
170 V AC
6
80 V AC
3
27 k
3ZX1012-0RW34-1AN1